An Empirical Study of Hot Water Supply Patterns and Peak Time in Apartment Housing with District Heating System (공동주택의 급탕부하 지속시간 및 부하 패턴에 관한 실증연구)

  • Kim, Sung-Min;Chung, Kwang-Seop;Kim, Young-Il
    • Journal of Energy Engineering
    • /
    • v.21 no.4
    • /
    • pp.435-443
    • /
    • 2012
  • The combination of space shortage and the high population density concentrated in urban areas of South Korea has resulted in the growth of large-scale high-rise residential complexes, naturally affecting water and hot water usage patterns as well. But the current designs for water and hot water supply in South Korea rely mostly on international design standards and data calculated on site due to the severe shortage of basic data in relation to actual use, which result in the frequent problem of the under-or over-design of water and hot water supply. The following study measures the hot water supplier's conditions and the user's heat usage to realize the amount of time required for hot water supply load generation and the pattern of actual use in order to create basic data for effective hot water supply facility design and maintenance.

Model Development of Daily and Hourly Energy Load for Department Stores (백화점 건물의 에너지 부하모델 개발)

  • 박화춘;이승수;김대진
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.12
    • /
    • pp.1088-1094
    • /
    • 2003
  • Case study was peformed to analyze energy load for department stores and develop energy load model to be applied to a cogeneration system. Energy loads of 14 departments were analyzed based on energy load sheets written by operators and energy load of one department store was measured through modem communication for a year. Energy load of department stores shows various variations depending on when they are opened or closed and, hours, days and months. In this paper, the measurement was compared with data in energy load sheets and resolved, and energy load model for a department store was built. It is important to use an accurate energy load model for an accurate feasibility study applying a cogeneration system to buildings.

Building Energy Demand Models for Offices in Korea (업무용 건물의 에너지 부하 모델)

  • Park, Hwa-Choon;Chung, Mo
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.5
    • /
    • pp.1-7
    • /
    • 2009
  • Energy demands for offices in Korea are surveyed and analyzed to generate communicational models for simulations. Daily energy loads of 13 office buildings scattered in the 6 largest cities in the country are surveyed and analyzed based on energy consumption log sheets. Detailed hourly loads that are frequently required when a detailed operation simulation is performed are measured using remote data acquisition processes for 3 offices. The complete load demand models of electricity, cooling, heating and hot water are established by combining the daily and hourly patterns based on the statistical behavior of the hourly patterns.

Comparison of Energy Demand Characteristics for Hotel, Hospital, and Office Buildings in Korea (호텔, 병원, 업무용 건물의 에너지 부하 특성 비교)

  • Park, Hwa-Choon;Chung, Mo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.10
    • /
    • pp.553-558
    • /
    • 2009
  • Energy demand characteristics of hotel, hospital, and office building are compared to provide guidelines for combining building in community energy system design. The annual, monthly, and daily energy demand patterns for electricity, heating, hot water and cooling are qualitatively compared and important features are delineated based on the energy demand models. Key statistical values such as the mean, the maximum are also provided. Important features of the hourly demand patterns are summarized for weekdays and weekends. Substantial variations in both magnitudes and patterns are observed among the 3 building types and smart grouping or combination of building type and size is essential for a successive energy supply.

Building Load Models for Hotels in Korea (국내 호텔 건물의 에너지 부하 모델)

  • Park, Hwa-Choon;Chung, Mo
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.4
    • /
    • pp.48-57
    • /
    • 2009
  • Energy demands for hotels in Korea are surveyed and statistically analyzed to develop calculation models for a simulation. Daily energy loads of 16 hotels located in Seoul, Busan, Daegu, Inchon, and Daejon are analyzed based on energy log sheets. Detailed hourly loads are field measured for 3 hotels that are carefully selected among the surveyed. One of the salient features for energy consumption by hotels is their weekly periodicity. Relatively large values of deviations are observed for both heat and electricity loads through the country. The mains factors are: location, hotel grade (luxuriousness) and insulation. Detailed quantitative information such are annual average, daily variation, and hourly patterns are provided.

Development of Energy Demand Models for Hospitals (병원 건물의 에너지 부하모델 개발)

  • Park, Hwa-Choon;Chung, Mo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.11
    • /
    • pp.636-642
    • /
    • 2009
  • Energy consumption data are surveyed and measured to develop energy demand models for hospital buildings as part of a complete package. Daily consumption profiles for electricity, heating, cooling and hot water are surveyed for 14 carefully chosen hospitals to establish energy demand patterns for a time span of a year. Then the hourly demand patterns of the 4 loads are field-measured for different seasons and statistically analyzed to provide higher resolution models. Used in conjunction with energy demand models for other types of buildings, the high resolution of 8760 hour energy demand models for a hospital for a typical year will serve as building blocks for the comprehensive model that allows the estimation of the combined loads for arbitrary mixtures of buildings.

Field Application of a Latent Heat Storage Tank for Load Shaving of Domestic Hot Water Supply in District Heating (지역난방 급탕공급 부하균등화를 위한 잠열축열조의 현장 적용)

  • Park, Sung Yong;Yoo, Hoseon
    • Plant Journal
    • /
    • v.17 no.2
    • /
    • pp.42-47
    • /
    • 2021
  • In terms of district heating operation, efficient production and supply of heat by alleviating the peak load at a specific time require an application technology that can solve the inconvenience of the user and the difficulties of the supplier. In this study, a 78 ℃ class PCM heat storage tank suitable among the technologies that can solve these problems was manufactured and applied to the hot water supply facility for apartments in district heating users. As a result of the application of this system, it was confirmed that the supply temperature was constant to the user compared to the existing supply method. In addition, it was confirmed that the reduction of the peak load due to load equalization reduced the heat supply margin of 10% in the existing heat supply facility. And the construction cost of the new heat supply facility and the construction cost of heat users is decreased by 5% and 10%, respectively.

Design Capacity Evaluation of 2-stage Hot Water Heat Exchanger in Apartment Mechanical Rooms with District Heating System (지역난방 공동주택에 설치하는 급탕 2단 열교환기의 용량 적정성 평가에 관한 연구)

  • Chung, Kwang-Seop;Sa, Ki-Yong;Kim, Lae-Hyun;Lee, Hoon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.8
    • /
    • pp.456-461
    • /
    • 2009
  • Recently, an increasing interest in district heating system has emerged rapidly, In this paper, the physical measurements and data to be monitoring through the internet were carried out with regard to hot water heating energy consumption at the three apartment housings with district heating system in Sang-am district of Seoul, Korea, Measurements were made of the thermal factors such as the pressure of heating pipe, flow rates, hot water temperature and etc, The objective of this study is to compare the design capacity of reheat exchanger with that of preheat exchanger in order to evaluate for the number of plates of two exchangers to be distributed properly.

Distribution of Hot Tap Water Load for District Heating Substation with Hot Tap Water 2-Stage Heat Exchanger (급탕 2단열교환방식 지역난방 열사용시설의 급탕부하 분배에 관한 연구)

  • Jeong, Dong-Hwa;Kim, Joo-Wan;Baik, Young-Jin;Lee, Young-Soo;Chung, Dae-Hun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.4
    • /
    • pp.297-302
    • /
    • 2011
  • According to the standards for district heating substation established by Korea District Heating Corporation, water heating supply systems at over 150 Mcal/h capacity must employ the 2-stage heat exchanger that improves the system efficiency by reusing the heat included in the return water of district heating system already used for space heating. In this paper, the operating characteristics of the system in accordance with the load distribution of two heat exchangers for pre-heating and re-heating cold city water are investigated. The results including mass flow rate, return temperature etc. help to manage district heating system economically.

태양열 구동 흡수식 냉방 시스템 실증

  • Gwak, Hui-Yeol
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2005.11a
    • /
    • pp.353-362
    • /
    • 2005
  • 태양열시스템은 하절기에 급탕과 난방 부하가 적거나, 거의 없어 시스템의 과열 문제가 야기 될 수 있다. 이를 해결하는 방안 중에 하나로 흡수식 냉방시스템을 이용하여 하절기 잉여열원을 활용하여 냉방하는 방법이 대두되고 있다. 태양열 냉방시스템은 전기에너지를 대체하는 효과 뿐 아니라 태양열 연간 이용 효율 극대화에도 크게 기여 할 수 있다. 본 고에서는 국내 기술로 최초로 개발 실용화된 중온용 단일 진공관형 태양열 집열기와 1중 효용 흡수식 냉방기를 이용하여 실증연구를 계획하였다. 태양열 냉방 실증을 위하여 단일 진공관형 태양열 집열기 집열면적 200m2, 축열조(태양열, 급탕, 냉수), 10RT급 냉방기, 냉각탑, 보조 보일러, 원격 제어 및 모니터링 등이 계획 되었다. 실증시험 중간 결과 태양열 냉방시스템은 하절기 맑은 날 하루 동안 약 5 - 6시간 안정적으로 가동 되었으며, 앞으로 온수급탕, 난방 시험을 거쳐 시스템 성능 및 경제성 평가를 통하여 유용성, 안정성 및 신뢰성이 검증 될 계획이다.