Geometric Effects of Compartment Opening on Fuel-Air Mixing and Backdraft Behavior (개구부의 기하학적 형상이 구획실의 연료-공기 혼합특성 및 백드래프트 거동에 미치는 영향)

  • Ha, Suim;Oh, Chang Bo
    • Fire Science and Engineering
    • /
    • v.33 no.1
    • /
    • pp.30-38
    • /
    • 2019
  • Mixing characteristics and backdraft dynamics were investigated using large eddy simulation for compartments initially filled with methane fuel. Four different opening geometries, i.e. conventional door opening case (Door) and the cases where horizontal door was implemented on the upper ($Slot_U$), middle ($Slot_M$) and lower part ($Slot_L$) of side wall, were considered in the simulations. For cases without ignition, the amounts of inflow oxygen and outflow fuel from the compartment opening were, from largest to smallest, Door > $Slot_U$ ~ $Slot_M$ > $Slot_L$. However, the fuel and oxygen were the best mixed for the $Slot_U$ case while the fuel and oxygen were not well mixed and in relatively separated two layers for the $Slot_L$ case. The global equivalence ratio defined by the amounts of fuel and oxygen in the compartment was not correlated reasonably with the peak pressure of backdraft. The peak pressure during backdraft was the highest for the $Slot_U$ case, a well mixed condition of fuel and air, and backdraft was not found for the $Slot_L$ where the pressure rise was not so high due to the mixing status. The peak pressures for the Door and $Slot_M$ cases were in between Door and $Slot_L$ cases. The peak pressure during backdraft was well correlated with the total amount of heat release until the instance of backdraft occurrence.

Evaluation of Design Fire Curves for Gas Fires in a Compartment Using CFAST (CFAST를 이용한 구획실 가스화재의 디자인 화재곡선 평가)

  • Baek, Bitna;Oh, Chang Bo;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.32 no.4
    • /
    • pp.7-16
    • /
    • 2018
  • In this study, the prediction performance of design fire curves (DF) was evaluated for gas fires in a compartment by using CFAST. The CFAST simulations adopted the 2-stage DF suggested by the previous study and the Quadratic and Exponential DF suggested by Ingason. It was found by comparing the simulation and experimental results that the overall prediction performance of the design fire cures for the spatially-averaged temperature and concentrations of $O_2$ and $CO_2$ was, from the most reasonable to the most inaccurate, 2-stage DF > Quadratic DF > Exponential DF. The CFAST simulation could not predict for the difference in the spatially-averaged temperature and concentrations of $O_2$ and $CO_2$ at door and inner side locations in a compartment. The CFAST simulations also showed a limitation in the prediction of the spatially-averaged temperature at lower layer and the concentration of CO.

A Numerical Study on the Effect of Volume Change in a Closed Compartment on Maximum Heat Release Rate (밀폐된 구획실의 체적변화가 최대 열발생률에 미치는 영향에 관한 수치해석 연구)

  • Yun, Hong-Seok;Nam, Dong-Gun;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.31 no.5
    • /
    • pp.19-27
    • /
    • 2017
  • The effects of changes in area and location of fire source, fire growth rate, and volume of compartment on the major fire characteristics, including heat release rate, in closed compartment fires were examined. To this end, a fire simulation using Fire Dynamics Simulator (FDS) was performed for ISO 9705 room with a closed opening. As main result, it was found that the changes in the area and location of fire source did not significantly affect the thermal and chemical characteristics inside the compartment, such as maximum heat release rate, total heat release, maximum temperature at upper layeras well as species concentrations. However, increasinthe fire growth rate and volume of compartment resulted in increase of the maximum heat release rate and total heat release, decrease in the limiting oxygen concentration and increase in the maximum CO concentration. Finally, a methodology for the application of fire growth curves to closed compartment fires was proposed by deriving the correlation of the maximum heat release rate expressed as a function of the fire growth rate and the volume ratio of compartment based on the ISO 9705 room.

The Influence of Zoning at Shafts of Super-tall Buildings on the Stack Effect and Stairwell Pressurization (초고층건물 샤프트의 수직구획이 연돌효과 및 급기가압 성능에 미치는 영향)

  • Kim, Beom-Kyue;Kim, Hak-Jung;Yeo, Yong-Ju;Leem, Chae-Hyun;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.92-98
    • /
    • 2012
  • This study analyzed the effect of zoning on the distribution of pressure differentials caused by stack effect and air pressurization in a center core type of 80 story super-tall building. The results showed that maximum pressure difference more than 250 Pa can be generated by stack effect without zoning. Zoning of stairwell only resulted in 10 Pa reduction of maximum pressure difference, however, zoning of both stairwell and EV shaft especially at the same floor revealed 50 % reduction in stack effect. It was also analysed that the minimum required air flow rate occurred when the stairwell temperature reached 50 % of temperature difference between indoor and outdoor.

Numerical Study on the Validity of Scaling Law for the Heat and Fluid Flow of Compartment Fires (구획화재 열유동에 대한 축소법칙의 유효성에 관한 수치해석 연구)

  • Ko, Gwon-Hyun
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.159-162
    • /
    • 2011
  • 본 연구에서는 환기 특성에 근거한 축소법칙의 유효성을 평가하기 위해 실규모 및 2/5 축소 구획에 대한 화재를 FDS를 이용하여 모사하고 기존의 실험 결과 및 해석 결과 상호간에 비교 분석을 수행하였다. 실규모 및 축소 모형에 대한 해석 결과를 비교할 때 구획 내부 유동 형태 등에 있어서 다소간의 차이를 보였으나 화염의 분출 거동 및 열유동 분포 등의 거시적인 특성에 대해서는 유사한 결과를 보여주었다.

  • PDF

Numerical Study on the Validity of Scaling Law for Compartment Fires (구획 화재의 상사 법칙 유효성에 관한 수치해석 연구)

  • Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.28 no.4
    • /
    • pp.29-34
    • /
    • 2014
  • In this study, to assess the validity of scaling law which was based on the ventilation factor and utilized in fields of compartment fires, numerical simulations were conducted on full- and 2/5 reduced-scale compartment fires using FDS and simulation results were compared with the previously published experimental data. The numerical modeling used in this study was verified by comparing the predicted temperature at several points of the upper layer with the experiment data. Temperature and concentration distribution inside of compartments and velocity profile at door of compartment are analyzed to assess the validity of scaling law. Comparison between the predicted results on the full- and reduced-scale compartments shows good agreements on the inner compartment flow patterns, outflowing flame patterns from the compartments, and vertical temperature distributions.

Examination on Effect of Horizontal Vent Position on Fire Phenomena in Enclosure (구획실 화재 현상에 대한 수평 개구부 위치의 영향 검토)

  • Park, Yu Mi;Lee, Chi Young
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2022.04a
    • /
    • pp.235-236
    • /
    • 2022
  • In the present study, the effect of horizontal vent position on fire phenomena in the enclosure with vertical and horizontal vents was examined using numerical simulation. Case 1 indicates the condition that the horizontal vent is in the center of the ceiling. Case 3 indicates the condition that the horizontal vent is far away from the vertical vent. Case 2 indicates the condition that the horizontal vent is installed between Case 1 and Case 3. The temperature distribution, smoke layer temperature, velocity distribution, and mass flow rate of horizontal vent flow were analyzed. In Case 2, the temperatures were lowest and the mass flow rate through the horizontal vent was largest. This is because the flame is inclined by the inflow through the vertical vent. Hence, to determine the proper horizontal vent location for the high smoke ventilation performance, the inflow through the vertical vent and its effect on flame behavior should be considered.

  • PDF

Changes in Fire Characteristics according to the Distance Between the Fire Source and Sidewall in a Reduced-Scale Compartment (축소 구획실에서 화원과 측벽의 거리에 따른 화재특성 변화)

  • Yun, Hong-Seok;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.33 no.1
    • /
    • pp.50-59
    • /
    • 2019
  • Experimental and numerical studies on the fire characteristics according to the distance between the fire source and sidewall under the over-ventilated fire conditions. A 1/3 reduced ISO 9705 room was constructed and spruce wood cribs were used as fuel. Fire Dynamics Simulator (FDS) was used for fire simulations to understand the phenomenon inside the compartment. As a result, the mass loss rate and heat release rate were increased due to the thermal feedback effect of the wall in the compartment fire compared to the open fire. As the distance between the fire source and sidewall was reduced, the major fire characteristics, such as maximum mass loss rate, heat release rate, fire growth rate, temperature, and heat flux, were increased despite the limitations of air entrainment into the flame. In particular, a significant change in these physical quantities was observed for the case of a fire source against the sidewall. In addition, the vertical distribution of temperature was changed considerably due to a change in the flow structure inside the compartment according to the distance between the fire source and sidewall.