• Title/Summary/Keyword: 고장 수용

Search Result 69, Processing Time 0.058 seconds

Adaptive Fault Accommodation Control for Flexible-Joint Robots (유연 관절 로봇의 적응 고장 수용 제어)

  • Yoo, Sung Jin
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.23 no.1
    • /
    • pp.46-50
    • /
    • 2013
  • This paper proposes an adaptive fault accommodation control approach for flexible-joint (FJ) robots with multiple actuator faults. It is assumed that the value and occurrence time of multiple actuator faults are unknown. An adaptive fault accommodation control scheme with prescribed performance bounds, which characterize the convergence rate and maximum overshoot of tracking errors, is designed to accommodate the actuator faults. From the Lyapunov stability theorem, it is proved that all signals of the closed-loop system are semi-globally uniformly ultimately bounded and tracking errors are preserved within prescribed performance bounds regardless of actuator faults.

Reliability Analysis of Distribution Systems by using FTA (FTA를 이용한 배전계통 신뢰도 분석)

  • Ku, Bon-Hui;Cha, Jun-Min;Kim, Hyung-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.247-249
    • /
    • 2008
  • 배전계통은 수용가에 전력을 공급하는 설비로서 계통의 안정적인 운영을 위하여 배전계통의 신뢰도를 산정하는 것은 중요한 의미를 갖는다. 본 논문에서는 배전계통을 구성하는 설비와 수용가의 전력 공급 유무에 따른 신뢰도를 산정하였다. Fault Tree Analysis(FTA)는 시스템의 고장을 해석하는 방법으로 사용된다. 시스템의 고장을 발생시키는 사건원인을 분석하여 Fault Tree(FT: 고장목)를 작성하고, 시스템을 구성하는 설비들의 고장확률 계산을 통하여 전 시스템의 신뢰성을 산정할 수 있다. 본 연구에서는 Relex 7.7 프로그램을 사용하여 FTA를 수행하였다.

  • PDF

Transient Stability of Industrial Plant on Voltage Disturbance in the Utility System (전력계통 전압외란에 대한 자가수용가의 과도 안정도 해석)

  • 조양행;정재길
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.12 no.3
    • /
    • pp.132-138
    • /
    • 1998
  • The dynamic analysis of stability in industrial power system is an important subject. In this paper, the effect of voltage dips for short duration (short-circuit) in the utility system on generators, synchronous motors of the industrial plant and the measures to be adopted to reduce the undesired effects of voltage dips re investigated. In the case of utility three-phase short-circuits of longer duration, both the generators and synchronous motors in the plant may become unstable. In order to avoid instability through fault clearing in the second zone time a decoupling device is necessary. The instability of voltage can be avoided with a well suited setting time of disconnecting device and load trip.

  • PDF

배전계통의 고장판단 및 사고복구 시스템

  • 이승재
    • 전기의세계
    • /
    • v.40 no.3
    • /
    • pp.57-61
    • /
    • 1991
  • 계통에 대한 정보, 즉 구간의 부하 상태, 차단기 및 스위치들의 현 개폐상태, 그리고 고장 검출기 동작상태 등은 통신망을 통하여 중앙 제어소로 전송되어지며 계통운용의 책임을 지고 있는 오퍼레이터(operator)는 이들 정보를 근거로 하여 계통의 현 상황을 파악하여 적절한 조치를 취하게 된다. 좀 더 자세히 말하면, 먼저 고장이 발생하지 않은 평상시(normal state)에는 계통의 부하 상태를 감시하여 운전손실 및 전압강하를 최소화 하는 계통으로의 변경을 원격조정 스위치 조작을 통하여 쉽고도 신속하게 실행시킴으로써 보다 효율적이고 경제적인 계통운전을 이룩할 수 있게 될 것이다. 또한 선로에 고장이 발생했을 경우, 변전소 차단기가 트립되기 전의 고장전류를 경험하게 되는 위치에 있는 스위치의 고장 검출요소(FD)가 동작하게 되며, 이러한 고장 검출기 동작상태, 스위치들의 현 개폐 상태 및 차단기의 트립 정보등은 중앙 제어소로 전송되어지며 오퍼레이터는 이들 정보로부터 고장구간을 판별하여 원격 조정 스위칭을 통하여 고장구간을 신속히 분리시키고, 정전구역에 대하여 운전 제약 조건을 위반하지 않는 복구계획을 수립하여 실행함으로써 보다 빠른 고장 위치 판단과 사고복구를 실현할 수 있으며 수용가의 공급 지장 시간을 최대한도로 줄여 배전 계통의 공급신뢰도를 높일 수 있다. 고장 발생시 이와 같은 일련의 과정은 크게 고장 구간 판별(Fault Location Identification) 및 정전 복구(Service Restoration)로 나눌 수 있으며 각각에 대하여 다음에 기술한다.

  • PDF

Fuzzy Logic based Faulted Section Identification Method (퍼지 로직을 이용한 고장구간 판단 기법)

  • Kim, Byeong-Goo;Son, Ju-Hwan;Lim, Seong-Il
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.156-157
    • /
    • 2011
  • 본 논문은 방사상으로 운용중인 배전계통에 1선 지락 고장시 퍼지 로직 알고리즘을 이용하여 고장구간을 판단하는 기법에 대해 제안하고 있다. 배전계통에 1선 지락 고장 발생 시 선로불평형 전류에 의해 고장구간 이후의 자동화개폐기에서 고장표시기가 오동작을 한다. 이로 인해 고장구간을 잘못 판단하여 수용가에 전력공급의 신뢰성이 줄어든다. PSCAD/EMTDC라는 전력해석용 툴을 이용하여 배전계통 모델링과 시뮬레이션을 하였고, 개폐기의 영상전류 크기를 통해 퍼지 로직이라는 인공지능기법을 이용하여 정확한 고장구간을 판단하는 기법을 제안한다.

  • PDF

Study on Calculation of Dynamic Penetration Limit of WTG and Applications of BESS in Power Systems (풍력발전의 전력계통 동적 수용한계 산정 및 BESS 적용방안 분석)

  • Gwon, Han Na;Choi, Woo Yeong;Kook, Kyugn Soo
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.1 no.1
    • /
    • pp.29-32
    • /
    • 2015
  • Since the characteristics of Renewable Energy Sources like wind turbine generators are very different from those of existing thermal power generators and their response to the sudden change of the frequency are not as good as that from thermal power generators. Especially when the penetration level of the wind power generation is substantially high, the output from the WTG would be possibly limited to keep the stability of power systems. For this, this paper implements the process for calculating the dynamic penetration limit of WTG and analyze the potential application of BESS for increasing the dynamic penetration limit of WTG.

A Study on Diagnosis Methods for a High Available Clustering Web Server (고가용성 클러스터 웹 서버의 로드밸런스에 대한 고장진단기법 연구)

  • Lee, Sang-Moon;Ko, Soung-Jun;Kang, Sing-Jun;Kwak, Tae-Young;Kim, Hag-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2000.07d
    • /
    • pp.2962-2964
    • /
    • 2000
  • 최근 웹의 사용이 일반화되면서 인터넷의 사용자가 급속히 증가하고 있어서. 기존의 단일 웹서버 방식에서는 막대한 접속 트래픽의 수용과 유연한 시스템 확장 등의 문제점이 예상되고 있다. 이와 함께 business-critical한 작업의 경우, 웹서버의 안정성 및 가용성 문제가 가장 중요한 문제로 지적되고 있어서 이러한 문제를 해결할 수 있는 웹전용 서버를 개발이 절대적으로 필요하다. 본 연구에서는 이를 위해. 급격한 트래픽 변화의 수용 및 웹서버의 확장성이 용이한 가상머신 개념과 고신뢰성의 시스템 운영을 위한 고장포용(fault-tolerant)기법을 적용하여 클러스터링 웹전용 서버를 구축하고, 특히 클러스터 웹서버의 부하를 분배해주는 로드밸런서의 고가용성 보장을 위해 heartbeat, fake, mon등의 기법을 이용하여 백업(backup)을 구현한다. 또한 구현된 시스템의 고성능 및 고가용성을 극대화하고. 시스템의 고장시 데이터 손실의 최소화와 이의 복구를 위해 고장 검출 및 진단 기법에 대한 방안을 제시한다.

  • PDF

The Analysis of Mal-Operation of Protection Relay for Detecting Disconnection of Neutral Grounding Reactor (전력용 변압기 중성점 리액터 단선 감시용 보호계전기 오동작 사례 분석)

  • Kang, Y.W.;Kwak, J.S.;Kim, G.Y.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.603-605
    • /
    • 2005
  • 전력수요의 증대에 따른 계동모의 확장에 따라 관련기기는 초고압 및 대용량화 추세에 있다. 이러한 관련기기들 중에서도 특히 154/22.9kV 전력용 변압기는 고장시 수용가의 정전범위가 방대하고 변압기 내부 고장의 복구비용 또한 막대하므로 경제적 손실은 물론 사회적 영향도 크다. 우리나라에서는 1980년 초기부터 154/22.9kV 전력용 변압기의 고장이 급증하였으며, 이러한 원인은 주로 직전접지 방식을 채택하고 있는 한전 계통에서 배전선의 지락고장에 의한 지락고장 전류가 변압기 중성점을 통하여 변압기에 충격을 가함으로써 변압기 권선 단락 절연파괴 및 ULTC 고장 등이 발생하는 것으로 밝혀졌다. 따라서 한전에서는 변압기 중성점으로 흐르는 지락고장전류의 저감을 위해 변압기 중성점 접지 리액터(NGR: Neutral Ground Reactor)를 설치하여 운전하고 있으며, 결과 변압기 고장이 크게 감소하였다. 그러나 모선 절체시 변압기 1, 2차측 차단기 Trip 고장이 발생하였으며, 고장 발생 원인은 NGR 보호계전기 59GT 계전기의 오동작에 의한 86T Lock Out 계전기 동자으로 변압기 1, 2차측 차단기 Trip 고장이 발생한 것으로 추정된다. 따라서 본 논문에서는 무부하 모선 차단시 59GT 계전기에 나타나는 이상 전압을 EMTP (electro-magnetic transient program)를 이용하여 분석하였다.

  • PDF

Finite Element Analysis of Internal Winding Faults in PAD-Type Distribution Transformer (유한요소법을 이용한 배전용 PAD변압기 권선고장시의 전자계해석)

  • Ha, Jung-Woo;Kim, Chul;Kim, Han-Deul;Shin, Pan-Seok;Lee, Byung-Sung;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2005.04a
    • /
    • pp.108-110
    • /
    • 2005
  • 배전용 변압기의 경우 고장 발생시 직접적인 수용가 측에 피해가 발생되며, 변압기 폭발시 인명 피해까지 우려되고 있다. 변압기 내부 고장으로 절연유가 분출될 경우가 가장 심각한 고장으로 이러한 피해를 방지하기 위해서는 내부 고장에 대한 정확한 해석이 필요하다. 본 연구에서 변압기 권선내에서 발생되는 고장을 유한요소 전자계해석 프로그램(FLUX2D)을 이용하여 해석하였다. 50kVA, 13200/230(V) 단강 변압기의 권선고장시 전자계해석, 1차측 권선고장(turn-to-earth)과 2차측 권선고장(turn-to-turn)을 모의하여 해석하였다. 또한, 권선 내부 고장 및 2차측 단락시 누설자속분포, 1차 및 2차측 고장전류, 권선간의 힘의분포 등을 해석하였다. 분석결과는 변압기의 절연설계 및 단락기계력에 대한 프레임 구조 설계를 위한 자료로 활용된다.

  • PDF

Series DC arc fault detection algorithm using time and frequency domain information (시간 및 주파수 영역 정보를 이용한 직렬 DC 아크 고장 검출 알고리즘)

  • Chae, Suyong;Park, Jinju;Park, Sukin;Han, Soobin
    • Proceedings of the KIPE Conference
    • /
    • 2015.07a
    • /
    • pp.427-428
    • /
    • 2015
  • 본 논문은 DC 배전시스템 내에서 발생할 수 있는 직렬 DC 아크 고장을 검출하기 위한 알고리즘을 제안한다. 직렬 DC 아크 고장은 동일 전위의 도선 또는 접속점의 노화 등으로 인해 발생하며, 아크 고장 에너지의 크기에 따라 수초 이내에 화재 사고를 유발할 수 있기 때문에 정확한 고장 검출을 통한 빠른 제거가 필요하다. 스위칭 전력변환 장치에서 발생하는 노이즈 성분에 의한 검출 알고리즘의 오동작 현상을 제거하기 위해 시간 영역에서의 전류 변화와 주파수 영역에서의 전류 크기 차이를 동시에 이용하여 직렬 DC 아크 고장 발생여부를 검출하게 된다. 제안 알고리즘은 5kW급 용량의 380V 저전압 DC 배전 시스템을 대상으로 검증하였다.