• Title/Summary/Keyword: 가변속냉동시스템

Search Result 10, Processing Time 0.024 seconds

Design of Predictive Controller for Effective Superheat Control of Variable Speed Refrigeration System (가변속냉동시스템의 효율적인 과열도제어를 위한 예측제어기 설계)

  • Choi, Jeong-Pil;Hua, Li;Jeong, Seok-Kwon
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.9-15
    • /
    • 2008
  • In this paper, we suggest PI control with a predictive controller to progress both energy saving and coefficient of performance(COP) in a variable speed refrigeration system. The capacity and superheat are controlled simultaneously and independently by an inverter and an electronic expansion valve respectively for saving energy and improving COP in the system. The refrigeration system has long dead time in superheat inherently. The dead time makes the system difficult to achieve the satisfactory quick control response, especially superheat control response. In order to solve this problem, we designed a predictive controller based on PI control to progress superheat control performance. The control performance was investigated through some experiments to verify the effectiveness of the predictive controller.

  • PDF

An Empirical Model for Decoupling Control of a Variable Speed Refrigeration System (가변속 냉동시스템의 비간섭제어를 위한 실험적 모델)

  • Hua, Li;Jeong, S.K.
    • Journal of Power System Engineering
    • /
    • v.10 no.3
    • /
    • pp.81-87
    • /
    • 2006
  • This paper deals with an empirical model for decoupling control to control the refrigeration system effectively. The conventional control schemes of the system are mainly focused on representative two control methods, superheat control and capacity control. The capacity control is basically conducted to respond partial loading conditions on the purpose of energy saving. The superheat control is mainly carried out to maintain maximum coefficient of performance (COP). In the variable speed refrigeration system, the capacity and the superheat are controlled by inverters and electronic expansion valves respectively for saving energy and improving cost performance. The capacity and superheat can not be controlled independently because of interfering loop when the compressor speed and opening angle electronic expansion valve is varied. Therefore, we suggest decoupling model to eliminate the interfering loop at first. Next, each transfer function in decoupling control model is obtained from number of experiments.

  • PDF

On-line Fault Detection and Diagnosis for Heat Exchanger of Variable Speed Refrigeration System Based on Current Information (전류정보를 이용한 가변속냉동시스템의 열교환기 실시간 고장 진단)

  • Lee, Dong-Gyu;Jeong, Seok-Kwon
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.88-94
    • /
    • 2007
  • This study deals with on-line fault detection and diagnosis for heat exchanger of variable speed refrigeration system. Conventional studies about fault of heat exchanger in refrigeration system have used temperature and pressure information. The temperature and pressure are able to be used valuably for faults detection of constant speed refrigeration system. However in case of variable speed refrigeration system, the temperature and pressure are no longer useful information for fault detection due to compensation effect of feedback controller. While current information is possible to detect faults of variable speed refrigeration system. The current information was detected in an inverter, it was used after transforming rms value. The faults of variable speed refrigeration system are divided into electrical faults and mechanical faults. We performed fault detection and diagnosis about heat exchanger among mechanical faults such as condenser fouling and evaporator fan fouling through some experiments.

  • PDF

State Equation Modeling and the Optimum Control of a Variable-Speed Refrigeration System (가변속 냉동시스템의 상태방정식 모델링과 최적제어)

  • Lee, Dan-Bi;Jeong, Seok-Kwon;Jung, Young-Mi
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.12
    • /
    • pp.579-587
    • /
    • 2014
  • This paper deals with precise analytical state equation modeling of a variable speed refrigeration system (VSRS) for optimum control in state space. The VSRS is described as multi-input and multi-output (MIMO) system, which has two controlled variables and two control inputs. First, the Navier-Stokes equation and mass flow rate were applied to each component of the basic refrigeration cycle to build a dynamic model. The dynamic model, represented by a differential equation, was transformed into the state equation formula. Next, a full-order state observer was built to estimate all of the state variables to compose an optimum control system. Then, an optimum controller was designed to minimize an evaluation function that has input energy and control error. Finally, simulations and experiments were conducted to verify the validity of the proposed modeling and designed optimum controller to regulate target temperature and superheat in a 1RT oil cooler system. The results show that the proposed method, state equation modeling and optimum control, is efficient to ensure optimal control performance of the VSRS.

Studies on the Performance Variation of a Variable Speed Vapor Compression System under Fault and Its Detection and Diagnosis (가변속 증기압축 냉동시스템에서 고장시의 성능변화와 고장 감지 및 진단에 관한 연구)

  • Kim Minsung;Kim Min Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.1
    • /
    • pp.47-55
    • /
    • 2005
  • An experimental study has been peformed to develop a scheme for fault detection and diagnosis(FDD) in a vapor compression refrigeration system. This study is to analyze fault effect on the system performance and to find efficient diagnosis rules for easy determination of abnormal system operation. The refrigeration system was operated with a variable speed compressor to modulate cooling capacity. The FDD system was designed to consider transient load conditions. Four major faults were considered, and each fault was detected over wide operating load range by separating the system response to the load change. Rule-based method was used to diagnose and classify the system faults. From the experimental results, COP degradation due to the faults in a variable speed system is severer than that in a constant speed system. The method developed in this study can be used in the fault detection of refrigeration systems with a variable speed compressor.