Browse > Article
http://dx.doi.org/10.12989/aer.2015.4.3.173

Simultaneous water and energy saving of wet cooling towers, modeling for a sample building  

Ataei, Abtin (Department of Energy Engineering, Graduate School of the Environment and Energy, Science and Research Branch, Islamic Azad University)
Choi, Jun-Ki (Department of Mechanical and Aerospace Engineering, University of Dayton)
Hamidzadeh, Zeinab (Department of Energy Engineering, Graduate School of the Environment and Energy, Science and Research Branch, Islamic Azad University)
Bagheri, Navid (Department of Energy Engineering, Graduate School of the Environment and Energy, Science and Research Branch, Islamic Azad University)
Publication Information
Advances in environmental research / v.4, no.3, 2015 , pp. 173-181 More about this Journal
Abstract
This article outlines a case study of water and energy savings in a typical building through a modelling process and analysis of simultaneous water-energy saving measures. Wet cooling towers are one of the most important equipments in buildings with a considerable amount of water and energy consumption. A variety of methods are provided to reduce water and energy consumption in these facilities. In this paper, thorough the modeling of a typical building, water and energy consumption are measured. Then, After application of modern methods known to be effective in saving water and energy, including the ozone treatment for cooling towers and shade installation for windows, i.e. fins and overhangs, the amount of water and energy saving are compared with the base case using the Simergy model. The annual water consumption of the building, by more than 50% reduction, has been reached to 500 cubic meters from 1024 cubic meters. The annual electric energy consumption has been decreased from 405,178 kWh to 340,944 kWh, which is about 16%. After modeling, monthly peak of electrical energy consumption of 49,428 has dropped to 40,562 kWh. The reduction of 18% in the monthly peak can largely reduce the expenses of electricity consumption at peak.
Keywords
water and energy saving; water and energy modeling; wet cooling towers; Simergy model;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Walsh, B.P., Surray, S.N. and O'Sullivan, D.T.J. (2015), "The water energy nexus, an ISO 50001 water case study and the need for a water value system", Water Resour. Ind., 10, 15-28.   DOI
2 Alaidroos, A. and Krarti, M. (2015), "Optimal design of residential building envelope systems in the Kingdom of Saudi Arabia", Energ. Buildings, 86, 104-117.   DOI
3 Alshamrani, O.S., Galal, K. and Alkass, S. (2014), "Integrated LCA - LEED sustainability assessment model for structure and envelope systems of school buildings", Build. Environ., 80, 61-70.   DOI
4 Ataei, A., Gharaie, M., Parand, R. and Panjeshahi, E. (2010), "Application of ozone treatment and pinch technology in cooling water systems design for water and energy conservation", Int. J. Energ. Res., 34(6), 494-506.   DOI
5 Boji, M. (2006), "Application of overhangs and side fins to high-rise residential buildings in Hong Kong", Civil Eng. Environ. Syst., 23(4), 271-285.   DOI
6 Conner, A. (2005), "Reducing cooling towers cost with the ozone technology", Clean Water Ozone Systems, Inc.
7 Ebrahimpour, A. and Maerefat, M. (2008), "Application of advanced glazing and overhangs in residential buildings", Energ. Convers. Manage., 52(1), 212-219.
8 Energyplus (2014) http://www.energyplus.gov/
9 Gude, V.G. (2015), "Energy and water autarky of wastewater treatment and power generation systems", Renew. Sust. Energ. Rev., 45, 52-68.   DOI
10 Haves, P., See, R. and Settlemyre, K. (2014), "Simergy - A graphicaluser interface for energyplus", Public interest energy research program; Final project report.
11 Heikkila, P. and Milosavljevic, N. (2001), "A comprehensive approach to cooling tower design", Appl. Therm. Eng, 21(9), 899-915.   DOI
12 Maestre, I.R., Blazquez, J.L.F., Gallero, F.J.G. and Cubillas, P.R. (2015), "Influence of selected solar positions for shading device calculations in building energy performance simulations", Energ. Buildings, 101, 144-152.   DOI
13 Panjeshahi, M.H. and Ataei, A. (2008), "Application of an environmentally optimum cooling water system design to water and energy conservation", Int. J. Environ. Sci. Tech., 5(2), 251-262.   DOI
14 Panjeshahi, M.H., Ataei, A., Gharaie, M. and Parand, R. (2009), "Optimum design of cooling water systems for energy and water conservation", Chem. Eng. Res. Des., 87(2), 200-209.   DOI
15 Parker, S.A. (1998), Ozone Treatment For Cooling Tower, The U.S. Department of Energy; Fed. Tech. Alert J., New York, NY, USA.
16 Rhodes, J.D., Gorman, W.H., Upshaw, C.R. and Webber, M.E. (2015), "Using BEopt (Energy Plus) with energy audits and surveys to predict actual residential energy usage", Energ. Buildings, 86, 808-816.   DOI
17 Viera, M.R., Guiamet, P.S., de Melle, M.F.L. and Videla, H.A. (2000), "Use of dissolved ozone for controlling planktonic and sessile bacteria in industrial cooling systems", Int. Biodeter. Biodegr., 44(4), 201-207.   DOI