Browse > Article
http://dx.doi.org/10.7836/kses.2015.35.3.057

An Operation Strategy of Udo Island Power System with the Introducing ESS  

LEE, DOHEON (Faculty of Wind Energy Engineering Graduate School, Jeju National University)
Kim, Eel-Hwan (Department of Electrical Engineering, Jeju National University)
Kim, Ho Min (Faculty of Wind Energy Engineering Graduate School, Jeju National University)
Oh, Sung-Bo (Department of Electrical Engineering, Jeju National University)
LEE, SEUNGMIN (Faculty of Wind Energy Engineering Graduate School, Jeju National University)
Publication Information
Journal of the Korean Solar Energy Society / v.35, no.3, 2015 , pp. 57-63 More about this Journal
Abstract
This paper presents a solution by introducing energy storage system(ESS) to solve an annual blackout due to a typhoon or electrical failure in Udo Island. This island is now receiving electrical power through undersea cables from the Jeju Island. During blackout period, ESS will supply the electricity. And it is necessary to estimate the ESS capacity and control the transient state for the operation of stable power system. For the verification of proposed method, ESS capacities have been estimated according to base load and the minimum capacity of only home appliance in Udo Island. Also, in case of restoring from the fault, the algorithm for synchronization is proposed. Finally, the simulation results by using the PSCAD/EMTDC program will show the feasibility.
Keywords
Energy storage system; Synchronization; Feasibility;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Report, KEPCO, "도서지역 디젤발전 신재생 접목을 위한 기준 정립 및 타당성 연구", 2012. 2.
2 KEPCO 한국전력, "우도 사업소 현황", 2013.
3 Panasonic battery manufacturer's data sheet.
4 Seung-Mo Kim, Seung-Jin Oh, Jong-Hak Lee, Jae-Min Ahn, Kyung-Min Jin, Byung-Gi Kwon, Chang-Ho Choi. POSCO ICT, "The application and Verification of the 2MVA BESS with Wind farm in Microgrid of Gapado. Jeju," Trans. KIPE, Nov. 2013.
5 JosepM. Guerrero, "Advanced Control Architectures for Interlligent Microgrids-Part1:Decentralized and Hierarchical control" IEEE,VOL. 60, NO.4, April, 2013.
6 KEPCO 한국전력, "송.배전용 전기설비 이용규정 : 별표 4 배전용전기설비 성능기준", 2014.