Development of Heliostat Aiming Point Allocation Scheme in Heliostat Field Control Algorithm for 200kW Tower Type Solar Thermal Power Plant  

Park, Young Chil (Department of Electrical & Information Engineering, Seoul National University of Science & Technology)
Publication Information
Journal of the Korean Solar Energy Society / v.34, no.3, 2014 , pp. 21-29 More about this Journal
Abstract
Heliostat field control algorithm is the logics to operate the heliostat field of tower type solar thermal power plant and it could include various methodologies of how to control the heliostat field so as to optimize the energy collection efficiency as well as to reduce the system operating cost. This work, as the first part of the consecutive works, presents heliostat aiming mint allocation scheme which will be used in the heliostat field control algorithm for 200kW solar thermal power plant built in Daegu, Korea. We first discuss the structure of heliostat field control system required for the implementation of aiming scheme developed in this work. Then the methodologies to allocate the heliostat aiming points on the receiver are discussed. The simulated results show that the heliostat aiming point allocation scheme proposed in this work reduces the magnitude of peak heat flux on the receiver more than 40% from the case of which all the heliostats in the field aim at the center of receiver simultaneously. Also it shows that, when the proposed scheme is used, the degradation of heliostat field optical efficiency is relatively small from the maximal optical efficiency the heliostat field could have.
Keywords
Tower type solar thermal power plant; Heliostat field; Heliostat field control system; Heliostat field control algorithm; Heliostat aiming point allocation scheme;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Garcia-Martin F. J., Berenguel M., Valverde, A. and Camacho E. F., "Heuristic Knowledge Based Heliostat Field Control for the Optimization of the Temperature Distribution in a Volumetric Receiver", Solar Energy, Vol. 66, No. 5, 1999, pp. 355-369   DOI   ScienceOn
2 PIER : California Energy Commission, "Renewable Energy : Solar two central receiver", October 1999
3 Park M. H., "Introduction of Daegu City Gas Power Tower Project", The Magazine of Korean Solar Energy Society, Vol. 9, No. 2, 2010, pp. 14-18
4 Park, Y. C., "Design of Heliostat Field for 200kW Tower Type Solar Thermal Power Plant", J. of the Korean Solar Energy Society, Vol. 32, No. 5, 2012, pp. 41-51   과학기술학회마을   DOI   ScienceOn
5 Park, Y. C., "Heliostat Control System", J. of the Korean Solar Energy Society, Vol. 29, No. 1, 2009, pp. 50-57   과학기술학회마을
6 Hong Y. P. and Park Y. C., "Measurement and Compensation of Heliostat Sun Tracking Error using BCS", J. of Institute of Control. Robotics and Systems, Vol. 18 No. 5, 2012, pp. 502-508   과학기술학회마을   DOI   ScienceOn