Browse > Article
http://dx.doi.org/10.7836/kses.2012.32.6.076

Analysis of Air Current Measurements at External Induction-Style Kitchen and Bathroom Vents  

Lee, Yong-Ho (School of Architecture & Civil Engineering, Kyungpook National University)
Kim, Seong-Yong (School of Architecture & Civil Engineering, Kyungpook National University)
Park, Jin-Chul (School of Architecture & Building Science, Chung-Ang University)
Hwang, Jung-Ha (School of Architecture & Civil Engineering, Kyungpook National University)
Publication Information
Journal of the Korean Solar Energy Society / v.32, no.6, 2012 , pp. 76-84 More about this Journal
Abstract
This study conducted experiments to measure air currents in an experimental building according to external conditions, types of induction ducts, and types of internal sockets by applying an external induction duct comprised of inducing openings and lines and induction units to the kitchen and bathroom vents at the rooftop of a super high-rise apartment building in order to help to improve the venting performance. The study also proposed the optimization of the external induction-style kitchen and bathroom vents capable of wind power generation. (1) As for air current distribution according to vent velocity changes, it increased the venting performance of the kitchen and bathroom by 1.0m/s at vent velocity of 2.0m/s or higher and allowed for wind power generation. (2)As for air current distribution according to external velocity changes, it increased the venting performance of the kitchen and bathroom by 1.2m/s at external velocity of 2.0m/s or higher and allowed for wind power generation. (3)As for air current distribution according to wind direction changes($0{\sim}180^{\circ}$), it was favorable for higher vent velocity when the angle between the external induction duct direction and prevailing wind direction was within ${\pm}30^{\circ}$. (4)As for air current distribution according to induction duct type, the[M1] type combining the inducing openings and lines with the induction units recorded the highest improvement effects in the kitchen and bathroom venting performance by increasing vent velocity by 46%. (5)As for air current distribution according to the changing types of internal sockets where the main ducts of the kitchen and bathroom are connected to the external induction ducts, the venturi tube type[Sv] increased vent velocity by 66% based on the smoothest external inflow.
Keywords
High-Rise Apartment; Kitchen and Bathroomexhaust duct; Induction trumpet; Induction pipe; Induction unit; Measured wind speed;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Lee, Y. H., Kim, S. Y., Park, J. C., Hwang, J. H., A Study on the Wind Power Generation Using Vertical Exhaust Air Duct of the High-Rise Apartments, Journal of the Korean Solar Energy Society, Vol.32, No.3, pp1-10, (2012)   과학기술학회마을   DOI
2 Kim, S. Y., Lee, Y. H., Park, J. C., Hwang, Airflow measuring analysis the rooftop kitchen and bathroom exhaust duct of residential building, SAREK, Sumer Annual Conference, pp798-801 (2012)
3 Park, J. H., Kim, J. W., Song, Y. W., Park, J. C., Hwang, J. H., A Experimental Studyon the Application of Small Wind Power System Combined Ventilatorin Super High-rise Apartment, SAREK, Sumer Annual Conference, pp725-728, (2012)
4 Shin, J. R., Park, J. J., Kim, H. Y., Kim, D. Y., Performance Study of Wind Augmentation Device for Building-integrated Wind Power, Journal of KFMA, Vol.15, No.4, pp.42-49, (2012)   과학기술학회마을   DOI
5 Nam, B. H., You, J. Y., You, G. P., Kim, Y. M., Wind-induced Variation of Velocity forTall-building with Openings with the CFD Simulations, Journal of WEIK, Vol. 15, pp.209-214, (2012)
6 Kim, H. G., The Korea Wind Resource MapandIts Application System, Journal of WEIK, Vol.15, pp.11-15, (2012)
7 Roh, J. W., Study on Improvement of Thermal Environment by using Wind-driven Natural Ventilation on the Atrium, Journal of KSES, Vol.32, No.1, pp.40-47, (2012)   과학기술학회마을   DOI
8 Jo, H. J., You, J. Y., You, K. P., Kim, Y. M., A Study of Wind energy Assessment according to numberand geometry of inlet to top floor of Tall Building, Journal of AIK, Vol.31, No.2, pp.107-108, (2011)