Browse > Article
http://dx.doi.org/10.7836/kses.2012.32.5.052

A Feasibility Study for the Application of the Cold-heat Storage System Considering the Real Operation Status of the Showcase  

Lee, Dong-Won (Korea Institute of Energy Research)
Kim, Jeongbae (Dept. of Energy System Engineering, Korea National University of Transportation)
Publication Information
Journal of the Korean Solar Energy Society / v.32, no.5, 2012 , pp. 52-58 More about this Journal
Abstract
Experimental study was performed to understand the real operation conditions of a showcase working usually in a convenient store and discount store. The purpose of this study was to show the possibility for practical use of cold-heat storage systems being operated for the showcase. To do that, evaporator and condenser temperatures were measured and the compressor electric power consumption were measured simultaneously. To use the ice storage system, the ice making process was typically operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was subcooled using the stored cold-heat after being discharged from the condenser during daytime. So, the cooling performance was increased with the sub-cooling of refrigerant during daytime,hence the actual running time of the compressor could be effectively decreased. Through the experiments, this study showed that the compressor electric power consumption during daytime could be transferred to nighttime for applying the refrigerant sub-cooling. So, for the convenient store, the maximum load transfer rates for each working cooler and showcase were estimated about 31.1% and 19.9% respectively. And for the discount store, the maximum load transfer rates for each refrigeration and freezing showcase were estimated about 34.1% and 49.0% respectively.
Keywords
Cold-heat storage system(CSS); Showcase; Sub-cooling; Load leveling; Load transfer rate;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Park, S-S, and Kim, Y-R., Technology of the ice storage system, Magazine of the SAREK, vol.30, no.6, pp.6-15, 2001.
2 Lee, D-W., Joo, M-C., Choi, B-J. and Kim, W., Sub-cooling effect using cold storage system, Proceedings of the SAREK, 2007, Summer Annual Conference, pp. 1067-1071, 2007.
3 Shin, Y-H., Oh, Y-G. and Park, K-H., Measurement and analysis of showcase field data, Proceedings of the SAREK, 2005, vol. 17, no. 5, pp. 436-443, 2005.