Browse > Article

A Performance Measurement and Evaluation of a 400RT Vertical type Geothermal System installed in a Complex Building Before Occupancy  

Hwang, Kwang-Il (Div. of Mechanical and Information Engineering, Korea Maritime University)
Shin, Dong-Keol (Graduate School of Korea Maritime University)
Kim, Joong-Hun (Samsung C&T)
Shin, Seung-Ho (Samsung C&T)
Jung, Myoung-Kwan (Samsung C&T)
Publication Information
Journal of the Korean Solar Energy Society / v.28, no.3, 2008 , pp. 7-14 More about this Journal
Abstract
400RT geothermal system which is the biggest capacity among on-operations at present in Korea is measured and evaluated on 23rd${\sim}$26th Jan. 2008 during those days building is not allowed owners and/or tenants to move in. The geothermal system is consist with vertical-typed 112 geothermal heat exchangers which are installed circle-like 1 row with 4m interval, and has 16 units of 25USRT geothermal-source heat pump(GSHP)s. And each 5 units of circulation pump are running for geothermal heat exchangers and hot water supplies. The followings are the results. The temperatures at G.L. -70m of 2 boreholes are varied quite similarly. The average temperature difference between inlet and outlet of geothermal pipes is $4.1^{\circ}C$, and that of hot water supply is $3.2^{\circ}C$, of Zone 3's each 4 GSHPs when being operated. Despite temperature fluctuations by heating loads, the average temperature difference between main pipes of inlet and outlet of geothermal heat exchangers is measured as $4.1^{\circ}C$. This study propose "Geothermal System COP" which includes not only consumed electric power by compressor but also circulation pumps and auxiliary utilities. By comparing the geothermal system COP with GSHP's performance specification, it is clear that the performances of GHSPs of this site are satisfied with the specification.
Keywords
Geothermal System; Complex Building; Performance Evaluation;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 에너지관리공단, http://racer.kemco.or.kr
2 김용식, 김중헌, 황광일, 주상복합 건축물에 적용된 지열이용 히트펌프시스템의 냉방성능 평가, 한국태양에너지학회 논문집, Vol. 26, No.4, pp. 9-16, 2006   과학기술학회마을
3 황광일, 우상우, 김중헌, 신승호, 김용식, 주상복합 건축물의 기초슬래브에 설치된 수평형 지열교환기의 계절별 성능평가, 한국태양에너지학회 논문집, Vol. 27, No.2, pp. 11-18, 2007   과학기술학회마을
4 北海道大学地中熱利用システム工学講座, 地中熱ヒートポンプシステム, Ohmsha, 2007
5 우상우, 황광일, 김중헌, 신승호, CFD 해석에 의한 수직형 지열교환기의 성능예측, 한국태양에너지학회 논문집, Vol.27, No.3, pp. 117-126, 2007   과학기술학회마을
6 Stephen P. Kavanaugh, Kevn Rafferty, Ground-Source Heat Pumps: Design of Geothermal Systems for Commercial and Institutional Buildings, ASHRAE, 1997
7 황광일, 김중헌, 신승호, 김용식, 건물 기초 슬래브에 설치된 수평형 지열교환기 성능의 경년변화, 대한건축학회논문집 계획계, 제23권 제5호, pp. 179-186, 2007. 5