Abstract
The purpose of this study is to present the simulation results and an overview of the performance assessment of the Ground-Source Heat Pump(GSHF) system. The calculation was performed for two design factors: the spacing between boreholes and the depth of the vertical ground heat exchangers. And the simulation was carried out using the thermal simulation code TRNSYS with new model of water to water heat pump developed by this study. As a result, it was anticipated that the yearly mean COPs of heat pump for heating and cooling are about 3.7 and 5.8 respectively and the heat pump can supply 100% of heating and cooling load all the year around.
Keywords
Borehole; Ground-Source Heat Pump; TRNSYS(TRNSYS);
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 J. Lund, B. Sanner, L. Rybach, R. Curtis and G. Hellstrom, Ground-sorce Heat Pumps - A World, Overview, Renewable Enrgy Worlrd, pp. 218-227, 2003
2 A. Murugappan, Implementing Ground Source Heat Pump and Ground Loop Heat Exchanger Models in the Energyplus Simulation Environment, M.S. These, Oklahoma state University, 2001
3 J. Warnelov, Ground-Coupled Heat Pump Market and Prospects in Europe, 7th IEA Heat Pump Conference, Beijing, 2002
4 이세균, 김대기, 우정선, 박상일,'1차원 모델에 의한 지중열교환기의 열거동 해석', 한국태양에너지학회 논문집, Vol.25, No. 1, pp. 97-104, 2005
5 University if Wisconsin-Maidison, TRNSYS 14.2 Reference manual, 1996