Browse > Article
http://dx.doi.org/10.12813/kieae.2014.14.6.099

The Individual Heat-recovery ventilation system of Residential Buildings  

Shin, U-Cheul (Dept. of Architecture Engineering, Daejeon Univ.)
Lee, Wang-Je (Solar Thermal Laboratory, Korea Institute of Energy Research)
Yoon, Jong-Ho (Dept. of Architecture Engineering, Hanbat National Univ.)
Baek, Nam-Choon (Solar Thermal Laboratory, Korea Institute of Energy Research)
Publication Information
KIEAE Journal / v.14, no.6, 2014 , pp. 99-104 More about this Journal
Abstract
Recently supply of low energy house is increasing which can enhance energy efficiency and indoor environment comfort. Low energy house have to secure air tightness as well as thermal performance so house become high airtightness and inevitably need heat recovery ventilator to enhance indoor air quality. However, most of current ventilation systems are one-click, controlling the entire space so it causes increasing of heating load and fan power which makes it hard to save energy. Thus, Individual Control system is required which can achieve both enhancing indoor air quality and decreasing heating load and electric fan power. Thereby, in this study, we analyzed the correlation between ventilation and fan power through mock-up experiment and measured ventilation load under individual control system. As a result, under the condition of $24^{\circ}C$ of indoor temperature for 6 month(November to April) in Daejeon, ventilation load by fan speed was $10.9{\sim}19.6kWh/m^2{\cdot}a$ when operated 24 hours and $7.6{\sim}13.7kWh/m^2{\cdot}a$ when operated 12 hours in night time. In addition, it is possible to reduce at most 60% of ventilation load under the individual control system; measured ventilation load was $7.4kWh/m^2{\cdot}a$ when operated 24 hours, and $5.5kWh/m^2{\cdot}$ when operated 12 hours in night time.
Keywords
Heat Recovery Ventilator; Airflow; Fan speed; Electic Power; Ventilation Load; Individual Control;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Lee, J. Y., Yoon, D. W., and Park, B. Y., 2007, Variation of Oxygen and Carbon Dioxide Concentration when 2 persons occupied in a Room and the Compensating Effects using Qxygen Generator Operation, Proceedings of the Korean Institute of Architectural Sustainable Environment and Building System, 2007-10. pp 139-144
2 Oh, B. K., Study on the Individual ventilation / Air conditioning system Housing pplication, Korean Association of Air Conditioning Refrigeration and Sanitary Engineers, Vol. 27, No. 6, pp 81-86
3 Regulation for Facility in Building, (Ministry of Land, Infrastructure, and Transport), Article 11, Paragraph 1, 2013. 09. 02
4 Kim, S. S., and Son, J. Y., 2009, A Performance Evaluation of Multidrop Chamber Ventilation System in Apartment Houses to Control Supply Air, Korean Soc. Living Environ. Sys., Vol. 16, No. 4, pp. 412-419
5 Hong, S. M., Yoon, D. W., and Kim, S. S., 2010, The Performance on the Individual Control of Room Ventilation Using Multidrop Chamber Operated by Motor Dampers in Residential House, Korean Soc. Living Environ. Sys., Vol. 17, No. 5, pp. 634-641
6 Yoon, D. W., Aha, B. W., 2004, The Evaluation on the Control Characteristics of Air Volume according to the Stroke Ratio of Damper Blade in Demand Controlled Ventilation(DCV) System, Achitectural Institute of Korea, Vol. 20, No. 9, pp 281-288
7 Kim, S. C., Yoon, J. H., Baek, N. C., and Shin, U. C., 2011, A Study on the Long-term Opearing plan of Ventilation System of Apartment House in terms of Energy Performance, Proceedings of the Korean Solar Energy Society, Vol. 31, No. 2, pp. 115-123
8 Cho, H., Choi, I. C., and Pang, S. K., 2011, Prediction of Energy Consumption and Indoor Ventilation Performance according to Individual Room Control Ventilation System in Apartment House, Korean Soc. Living Environ. Sys., Vol. 18, No. 4, pp. 411-418
9 http://www.kemco.or.kr, Korea Energy Managerment Corporation
10 Ministry of Trade, Industry and Energy, 2013, Conversion standard of energy calories (Paragraph 1 of Article 5)
11 http://www.kma.go.kr(Meteorological Administration)
12 http://phiko.kr, Passive house Institute Korea
13 Heat-recovery ventilators, 2012, Korean Standards Information Center KS B 6879