Browse > Article

Numerical Study on Ventilation Method for Temperature Control of HRSG Building  

Kim, Chul Hwan (Dept. of Mechanical Design and Manufacturing Engineering, Changwon National University)
Lee, Jong Wook (Dept. of Mechanical Design and Manufacturing Engineering, Changwon National University)
Choi, Hoon Ki (Dept. of Mechanical Design and Manufacturing Engineering, Changwon National University)
Yoo, Geun Jong (Dept. of Mechanical Design and Manufacturing Engineering, Changwon National University)
Publication Information
Journal of Korean Society of Occupational and Environmental Hygiene / v.19, no.3, 2009 , pp. 240-249 More about this Journal
Abstract
HRSG(Heat Recovery Steam Generator) building is large enclosed structure included various heat sources. This building needs to appropriately keep internal air temperature for worker's safety and operability of control devices. In this study, ventilation analysis is performed to find proper ventilation method for temperature control. Ventilation analysis is applied to entire internal space of the building with standard $k-{\varepsilon}$ model and enhanced wall treatment because of large size of the structure. And the ventilation method is considered natural and forced convection with two louver structures which has damper or not. Louver structure affect directly air circulation in near HRSG and lower region of the building. Forced ventilation provides strong inertial force which cause upward airflow. From the analysis, it is found that design requirement for internal air temperature can be satisfied by forced ventilation method with louver structure without damper.
Keywords
ventilation; HRSG building; numerical analysis; k-$\varepsilon$model; louver structure;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Q. Chen, 1995, Comparison of Different k-$\epsilon$ Models for Indoor Air Flow Computation, Numerical Heat Transfer, 28, 353-369   DOI
2 T. Yilmaz; S. M. Fraser, 2007, Turbulent natural convection in a vertical parallel-plate channel with asymmetric heating, Heat and Mass Transfer, 50, 2612-2623   DOI   ScienceOn
3 Fluent Inc. 2006 Fluent 6.3 User's guide
4 B. E. Launder and D . B.Spalding, 1974, The Numerical Computation of Turbulent Flows, Compter methods in Applied Mechanics and Engineering, 3, 269-289   DOI   ScienceOn
5 D. Blay; S. Mergui; C. Niculae, 1992, Confined turbulent mixed convection in the presence of a horizontal buoyant wall jet, ASME Fundamentals of Mixed Convection, 213, 65-72
6 G. M. Stavrakakis; M. K. Koukou; M. Gr. Vrachopoulos; N. C. Markatos, Natural cross-ventilation in buildings: Building-scale experiments, numerical simulation and thermal comfort evaluation, 2008
7 J. J. Costa; L. A. Oliveira; D. Blay, 1999, Test of several versions for k-εtype turbulence modeling of internal mixed convection flows, Int. J. Heat and Mass Transfer, 42, 4391-4409   DOI   ScienceOn
8 J. H. Kang; S. J. Lee, 2008, Improvement of natural ventilation in a large factory building using a louver ventilator, Building and Environment, 43, 2132-2141   DOI   ScienceOn
9 P. L. Betts; L. H. Bokhari, 2000, Experiments on turbulent natural convection in an enclosed tall cavity, Heat and Fluid Flow, 21, 675-683   DOI   ScienceOn
10 Wei Zhang, Qingyn Chen, 2000, Large eddy simulation of airflow with a filtered dynamic subgrid scale model, Int. Heat Mass Transfer, 43, 3219-3231   DOI   ScienceOn
11 김철환. 유근종. 최훈기, 2005, 보일러빌딩 내부 환기현상에 관한 수치적 연구, 한국산업위생학회지, 15(3), 239-249
12 Q. Chen, 1996, Prediction of Room Air Motion by Reynolds-Stress Models, Building and Environment, 31, 233-244   DOI   ScienceOn