Abstract
In this study, the comparative analysis, among the design standard value of distribution power, the calculated value from the measurement data of strand and the empirical data of the distribution line itself, have been performed for the elastic coefficients and linear expansion coefficients of distribution line conductors. The empirical values of elastic coefficients were lower about 10.6%(892kgf/mm2) than those of the design standard value of the distribution power and there were a little difference between the empirical values of linear expansion coefficients and the design standard value of the distribution power. From the above results, it could be concluded that the empirical values of conductor characteristics should be used in the dip design and installation of distribution line.