3-Phase RMS Voltage Measurement Method of Virtual Frequence using Instantaneous Power Component Concept  

Park, Seong-Mi (Dept. of Lift Engineering, Korea Lift College)
Yang, Ji-Hoon (Dept. of Electrical Engineering, Chonnam University)
Park, Sung-Jun (Dept. of Electrical Engineering, Chonnam University)
Publication Information
Journal of the Korean Society of Industry Convergence / v.22, no.3, 2019 , pp. 251-257 More about this Journal
Abstract
This paper proposes a new measurement method using virtual power concept to measure the effective value of 3-phase voltage with variable frequency. The conventional effective value measurement method uses a method of integrating data sampled during one or half cycle of the power voltage and averaging it. In this method, since the effective voltage is calculated every cycle, a time delay occurs in the measured effective voltage and it is s a problem to measure the effective value of a device whose frequency varies from time to time, such as a generator. The proposed 3-phase voltage rms measurement method has an advantage that it can measure accurate voltage RMS value regardless of measurement frequency variation. In particular, there is an advantage in that it is possible to measure a 3-phase effective voltage rather than an average value of the effective voltage of each phase in a 3-phase unbalance voltage. In addition, the validity of the proposed method is verified by using the Psim simulation tool and the experimental results are analyzed by applying the proposed measurement algorithm to the actual three phase synchronous generator voltage measurement experiment.
Keywords
RMS calculation; Synchronization; Variable frequency; Time delay;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Engelbart D. Bhabha Z. Watanabe H. & Zhou I, "Sclaff : Wearable, Bayesian methodologies," Journal of Symbiotic Certifiable Communication, 66(6). pp. 156-194. (2003).
2 J. M. Kim. Y. S. Shin & J. P. Kim. "Development of access points," In Proceedings of the Conference on Interactive Models," pp. 12-14, (2015).
3 Bdew, "Generating plants connected to the medium-voltage network," Technical Guideline, pp. 1-130, (2008).
4 Korea Electric Power Corporation, "Distributed power supply grid connection technology standard," pp. 1-18, (2015).
5 H. Hegedus, "Comparison of RMS value measurement algorithms of non-coherent sampled signals," Measurement Science Review, Vol. 11, No. 3, pp. 79-84, (2011).   DOI
6 K. Ding, K. W. E. Cheng, X. D. Xue, and B. P. Divakar, "A novel detection method for voltage sags", in 2nd International Conference on Power Electronics Systems and Application, pp. 250-288, (2006).
7 J. Y. Lee, "A study on voltage sag detection of power quality compensator", Conference on Power Electronics, pp. 760-763, (2004).
8 S. H. Cho, "Equivalent 10-Hz flicker index calcultation using half-cycle sliding window and recursive RMS method", Journal of Electrical Engineering & Thechnology, Vol. 60, No. 11, pp. 2017- 2020, (2011).
9 V. Yang, "Coherent sampling solution for an electric power system", Texas Instruments Application Report SLAA570, pp. 1-18, (2012).
10 W. Fan, "Frequency-response character -istics and error estimation in RMS measurement", IEEE Transactions on Industry Applications, Vol. 19, No. 4, pp. 1569-1578, (2014).