Improvement of Heat Pump Heating Performance by Selective Heat Storage Using Air Heat of Inside and Outside Greenhouse  

Kwon, Jin Kyung (Protected Horticulture Research Institute, NIHHS, RDA)
Kim, Seung Hee (Protected Horticulture Research Institute, NIHHS, RDA)
Jeon, Jong Gil (Agricultural Safety Engineering Division, NAAS, RDA)
Kang, Youn Koo (Protected Horticulture Research Institute, NIHHS, RDA)
Jang, Kab Yeol (Mushroom Research Division, NIHHS, RDA)
Publication Information
Journal of Bio-Environment Control / v.26, no.4, 2017 , pp. 353-360 More about this Journal
Abstract
In this study, the design and performance test of the air to water heat pump capable of producing hot water for greenhouse heating by using the surplus solar heat inside the greenhouse and the air heat outside greenhouse as the selective heat source were conducted. The heat storage operations using the surplus solar heat and the outside air heat were designed to be switched according to the setting temperature of the greenhouse in consideration of the optimum temperature range of the crop. In the developed system, it was possible to automatically control the switching of heat storage operation, heating and ventilation by setting 12 reference temperatures on the control panel. In the selective heat storage operation with the surplus solar heat and outside air heat, the temperature of thermal storage tank was controlled variably from $35^{\circ}C$ to $52^{\circ}C$ according to the heat storage rate and heating load. The heat storage operation times using the surplus solar heat and outside air heat were 23.1% and 30.7% of the experimental time respectively and the heat pump pause time was 46.2%. COP(coefficient of performance) of the heat pump of the heat storage operation using the surplus solar heat and outside air heat were 3.83 and 2.77 respectively and was 3.24 for whole selective heat storage operation. For the comparative experiment, the heat storage operation using the outside air heat only was performed under the condition that the temperature of the thermal storage tank was controlled constantly from 50 to $52^{\circ}C$, and COP was analyzed to be 2.33. As a result, it was confirmed that the COP of the heat storage operation using the surplus solar heat and outside air heat as selective heat source and the variable temperature control of the thermal storage tank was 39% higher than that of the general heat storage operation using the outside air heat only and the constant temperature control of the thermal storage tank.
Keywords
coefficient of performance; electric power consumption; greenhouse climate; surplus solar heat; ventilation;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Gracia, J.L., De la Plaza, L.M. Narvas, R.M. Benavente and L. Luna. 1998. Evaluation of the feasibility of alternative energy sources for greenhouse heating. J. Agric. Engng Res. 69:107-114.   DOI
2 Kang, Y.K., Y.S. Ryou, G.C. Kang, Y. Paek, and Y.J. Kim. 2007. Heating performance of horizontal geothermal heat pump system for protected horticulture. J. of Biosystems Eng. 32(1):30-36 (in Korean).   DOI
3 Kawashima, H., M. Takaichi, M. BaBa, K. Yasui and Y. Nakano. 2008. Effects of energy saving and the reduction of carbon dioxide emissions with a hybrid-heating system using an air-to-air heat pump for greenhouse heating. Bulletin of the National Institute of Vegetable and Tea Science 7:27-36 (in Japanese).
4 Kawashima, H., M. Takaichi and K. Yasuba. 2011. Performance of air-to-air heat pump for tomato greenhouse cooling and reduction of night-cooling load by mulch to control soil heat flux. Bulletin of the National Institute of Vegetable and Tea Science 10:95-104 (in Japanese).
5 Korean Solar Energy Society(KSES). 2017. Korean standard weather data. http://www.kses.re.kr/data_06/list_hi.php (in Korean).
6 Kwon, J.K., G.H. Kang, J.P. Moon, Y.K. Kang, C.K. Kim, and S.J. Lee. 2013. Performance Improvement of an Air Source Heat Pump by Storage of Surplus Solar Energy in Greenhouse. Protected Horticulture and Plant Factory 22(4):328-334 (in Korean).   DOI
7 Lim, M.Y., H.K. Chung, M.S. Son, S.B. Lee, G.J. Kim, B.S. Kim, Y.B. Kim, and B.R. Jeong. 2009. Effect of heating by nano-carbon fiber infrared lamp on growth and vase life of cut roses and heating cost. Journal of Bio-Environment Control 18(1):1-8 (in Korean).
8 Ministry of Agriculture, Food and Rural Affairs(MAFRA). 2016b. Cultivation status of floricultural crop in 2015. ed. Sejong, Korea (in Korean).
9 Marsh, L.S. and S. Singh. 1994. Economics of greenhouse heating with a mine air-assisted heat pump. Trans. of the ASAE 37(6):1959-1963.   DOI
10 Ministry of Agriculture, Food and Rural Affairs(MAFRA). 2016a. Greenhouse status for the vegetable grown in facilities and the vegetable productions in 2015. ed. Sejong, Korea (in Korean).
11 Peak, Y., J.G. Jeon, and N.K. Yun. 2011. Energy saving effect of carbon nano heating pipe for heating of greenhouse. Jou. of Korean Soc. of Mechanical Technology 13(3):107-111 (in Korean).
12 Ryou, Y.S., Y.K. Kang, G.C. Kang, Y.J. Kim, and Y. Paek. 2008. Cooling performance of horizontal type geothermal heat pump system for protected horticulture. Journal of Bio-Environment Control 17(2):90-95 (in Korean).
13 Willits, D.H. and Y.R. Gurjer. 2004. Heat pumps for the heating and night-cooling of greenhouse crops: a simulation study. Trans. of the ASAE 47(2):575-584.   DOI
14 Suh. W.M., Y.H. Bae, Y.S. Ryou, S.H. Lee, H.T. Kim, Y.J. Kim and Y.G. Yoon. 2011. Estimation of surplus solar energy in greenhouse(II). Journal of Bio-Environment Control 20(2):83-92 (in Korean).
15 Tong, Y., T. Kozai, N. Nishioka, and K. Ohyama. 2011. Greenhouse heating using heat pumps with a high coefficient performance(COP). Biosystems Engineering 106:405-411.