Browse > Article
http://dx.doi.org/10.3741/JKWRA.2022.55.S-1.1167

Risk analysis of the old pipe networks for priority determination of renovation  

Lee, Jae Hyeon (Department of Civil Engineering, Cheongju University)
Lee, Sang Mok (Department of Civil Engineering, Cheongju University)
Park, Byung Soo (Department of Civil Engineering, Gangwon State University)
Kwon, Hyuk Jae (Department of Civil Engineering, Cheongju University)
Publication Information
Journal of Korea Water Resources Association / v.55, no.spc1, 2022 , pp. 1167-1175 More about this Journal
Abstract
In this study, management index method has been developed to estimate the level of deterioration, applied to Cheongju city, and compared with the previous estimation methods of deterioration level of water distribution system. From the results, distribution systems of Yullyang, Naedeok1 and Yongam2 are found to be seriously deteriorated. And it was also found that probability of pipe breakage was estimated as 3.21%, 4.64% which is highest level at the steel pipe of 200 mm and 300 mm diameter. It was found that risk degree was estimated as 0.2609, 0.2644 by using management index method in Naedeok1 which is the most dangerous distribution system in the city. It was also found that results of risk analysis by management index method have been similar with the results of safety analysis by reliability method and indirect estimation method of deterioration level. Therefore, newly developed management index method can be applied and may be useful to the estimation of deterioration level for the future maintenance and management of water distribution system.
Keywords
Pipe network; Management index; Deterioration; Risk analysis;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Kim, E.S., Lee, S.H., and Yoon, K.Y. (2014). "Assessment of the deterioration of large-diameter pipe networks (I): Development of an assessment model." Journal of the Korea AcademiaIndustrial cooperation Society, Vol. 15, No. 1, pp. 482-487.   DOI
2 Kim, J.H., Ryu, T.S., Kim, J.H., and Ha, S.R. (2007). "Characteristics of pit corrosion and estimation models of corrosion depth in buried water pipes." Journal of the Korean Society of Water and Wastewater, Vol. 21, No. 6, pp. 689-699.
3 Korean Cast Iron Pipe Cooperation (KCIP) (2012). Handbook of ductile cast iron pipe.
4 Kwon, H.J., and Lee, K.J. (2021). "Safety analysis and deterioration evaluation of water pipe for improvement according to service year." Journal of Korea Water Resources Association, Vol. 54, No. 8, pp. 589-597.   DOI
5 Lee, H.D., Bae, C.H., Hong, S.H., Hwang, J.W., and Kwak, P.J. (2004). "Residual life assessment on cast iron pipes of water distribution system." Journal of Korean Society on Water Quality, Vol. 20, No. 3, pp. 206-214.
6 Ministry of Environment (ME) (2019). Inspection manual of water pipe.
7 Park, S.W., Kim, T.Y., Lim, K.Y., and Jun, H.D. (2011). "Fuzzy techniques to establish improvement priorities of water pipes." Journal of Korea Water Resources Association, Vol. 44, No. 11, pp. 903-913.   DOI
8 Romanoff, M. (1957). Underground corrosion. National Bureau of Standards Circular 579, US Government Printing Office, Washington D.C., U.S.