Browse > Article

Residual Life Assessment on Cast Iron Pipes of Water Distribution System  

Lee, Hyun-Dong (Korea Institute of Construction Technology Construction Environment Research Dept.)
Bae, Chul-Ho (Korea Water Resources Corporation, Korea Institute of Water and Environment)
Hong, Seong-Ho (Soongsil Uni. Env. & Che. Eng.)
Hwang, Jae-Woon (Korea Institute of Construction Technology Construction Environment Research Dept.)
Kwak, Phill-Jae (Korea Institute of Construction Technology Construction Environment Research Dept.)
Publication Information
Abstract
Residual wall thicknesses, corrosion rates, and residual life of thirty four samples of cast iron pipes(CIPs) and ductile cast iron pipes(DCIPs) collected from water mains of B city were studied to estimate their remaining service life or optimum time of rehabilitation. The internal maximum corrosion depths of samples measured using a dial gauge after shot blasting were twice higher than the external in most cases. Therefore corrosion of water pipes was much more affected by internal water quality than soil. Residual wall thicknesses of DCIPs were higher than those of CIPs. That reason was thought to be that DCIPs have been protected from internal corrosion by lining cement mortar. Residual life calculated by maximum corrosion rate was ranged up to 44 years with 12.40 years average. Since most CIPs were much deteriorated, rehabilitation plan should be established soon in B city. Residual life of DCIP was 33.52 years average. When cement mortar lining is used up by neutralization of DCIPs. DCIP also should be rehabilitated.
Keywords
Remining service life; Residual Life; Residual wall thickness; Corrosion rate;
Citations & Related Records
연도 인용수 순위
  • Reference
1 한국물학술단체연합회/한국수자원공사, 21세기의 물, 제8회 세계 물의 날 기념 물 심포지엄 (2000)
2 2002 상수도통계, 환경부 (2003)
3 이현동, 지재성, 서규태, 정원식, 정해룡, 배수시스템내 부식영향 수질인자의 변화 특성, 대한환경공학회지, 20(8), pp. 1151-1160 (1998)
4 Dempsey, P., Manook, B.A., Assessing the Condition of Cast Iron Pipes, WRc, United Kingdom (1986)
5 AWWA Research Foundation, Internal corrosion of water distribution systems, Second Edition. U.S.A (1996)
6 이현동 등, 상수도관로의 부식 및 노후도 예측모델 개발, G-7환경공학 기술개발사업, 환경부 (2002)
7 정원식, 이현동, 유명진, 곽필재, 토양환경영향인자를 이용한 상수도관 외부부식 평가에 관한 연구, 대한환경공학회지, 23(10), pp. 1611-1619 (2001)
8 김만기, 이현동, 정원식, 최준향, 상수도시스템의 누수저감 방안에 관한 연구(1), 대한환경공학회 2002년도 춘계학술연구발표회 논문집(1), pp. 171-172 (2002)
9 Kelly, D., Day, O., External corrosion in distribution systems, AWWA, 81(10), pp. 45-52 (1989)
10 이현동, 정원식, 김만기, 배철호, 곽필재, 김중훈, 김응석, 상수도관로의 관체부식 평가기법에 관한 연구, 대한환경공학회 2000년 추계학술연구발표회 논문집(I), pp. 485-486 (2000)