Browse > Article
http://dx.doi.org/10.5762/KAIS.2018.19.8.312

Operation Scheduling in a Commercial Building with Chiller System and Energy Storage System for a Demand Response Market  

Son, Joon-Ho (LG Electronics)
Rho, Dae-Seok (Department of Electrical Engineering, Korea University of Technology and Education)
Publication Information
Journal of the Korea Academia-Industrial cooperation Society / v.19, no.8, 2018 , pp. 312-321 More about this Journal
Abstract
The Korean DR market proposes suppression of peak demand under reliability crisis caused a natural disaster or unexpected power plant accidents as well as saving power plant construction costs and expanding amount of reserve as utility's perspective. End-user is notified a DR event signal DR execution before one hour, and executes DR based on requested amount of load reduction. This paper proposes a DR energy management algorithm that can be scheduled the optimal operations of chiller system and ESS in the next day considering the TOU tariff and DR scheme. In this DR algorithm is divided into two scheduling's; day-ahead operation scheduling with temperature forecasting error and operation rescheduling on DR operation. In day-ahead operation scheduling, the operations of DR resources are scheduled based on the finite number of ambient temperature scenarios, which have been generated based on the historical ambient temperature data. As well as, the uncertainties in DR event including requested amount of load reduction and specified DR duration are also considered as scenarios. Also, operation rescheduling on DR operation day is proposed to ensure thermal comfort and the benefit of a COB owner. The proposed method minimizes the expected energy cost by a mixed integer linear programming (MILP).
Keywords
Chiller System; Demand Response; Energy Management System; Energy Storage System; MILP;
Citations & Related Records
Times Cited By KSCI : 7  (Citation Analysis)
연도 인용수 순위
1 N. S. Kim, "Effect of SIC Errors to Cooperative NOMA systems", The Journal of The Institute of Internet, Broadcasting and Communication, Vol.17, No.5, pp.35-42, 2017. DOI: https://dx.doi.org/10.7236/JIIBC.2017.17.5.35   DOI
2 S. J. Oh, "Design of the Smart Application based on IoT", The Journal of The Institute of Internet, Broadcasting and Communication, Vol.17, No.5, pp.151-155, 2017. DOI: https://dx.doi.org/10.7236/JIIBC.2017.17.5.151   DOI
3 Jonson controls, Demand Response Reference Information. [Internet]. Demand Response in Commercial Buildings, Available From: https://pdfs.semanticscholar.org/presentation/5ae1/0e4c9adab6ba7e152601c8e60543b6676cfd.pdf (accessed Sep., 28, 2007)
4 R. Walawalkar, S. Fernands, N. Thakur, K. R. Chevva, "Evolution and current status of demand response (DR) in electricity markets: Insights from PJM and NYISO", ENERGY, Vol.35, No.4, pp.1553-1560, April 2010. DOI: https://dx.doi.org/10.1016/j.energy.2009.09.017   DOI
5 J. W. Kim, "A Study on Deterministic Utilization of Facilities for Allocation in the Semiconductor Manufacturing", Journal of the Society of Korea Industrial and Systems Engineering, Vol.39, No.1, pp.153-161, 2016. DOI: https://dx.doi.org/10.11627/jkise.2016.39.1.153   DOI
6 Federal Energy Regulatory Commission (FERC), Demand Response Reference Information. [Internet]. Assessment of Demand Response and Advanced Metering (Staff Report), Available From: http://www.ferc.gov/legal/staff-reports/09-07-demand-response.pdf (accessed Sep., 28, 2007)
7 Korea power exchange (KPX), Demand Response Market Reference Information. [Internet]. Demand Response Market Operation Regulation., Available From: http://dr.kmos.kr/main/market_01.htm (accessed Nov., 1, 2014)
8 J. Son, R. Hara, H. Kita, E. Tanaka, "Energy management considering demand response resource in commercial building with chiller system and energy storage systems", Proc. of The 2nd IEEE Conference on Power Engineering and Renewable Energy (ICPERE) 2014, pp.66-69, Dec. 2014 DOI: https://dx.doi.org/10.1109/ICPERE.2014.7067239   DOI
9 J. Son, R. Hara, H. Kita, "Determination of the optimal DR capacity for a commercial building with chiller system and energy storage system", IEEJ Transactions on Electrical and Electronic Engineering, Vol.12, No.4 pp.536-545, Jul. 2017. DOI: https://dx.doi.org/10.1002/tee.22409   DOI
10 S. Taylor, P. Dupont, B. Jones, T. Hartman, M. Hydeman, "Cool Tools Chilled Water Plant Design and Specification Guide", PG&E Cool Tools Report CT-016, May 2000
11 J. Son, R. Hara, H. Kita, E. Tanaka, "Operation scheduling considering demand response in a commercial building with chiller system and energy storage system", Proc. of 2015 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), pp.1-5, Dec. 2015 DOI: https://dx.doi.org/10.1109/APPEEC.2015.7381008   DOI
12 "Thermal Environmental Conditions for Human Occupancy", The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard: ANSI/ASHRAE 55-1992
13 N. S. Kim, "Optimum Power Allocation of Cooperative NOMA Systems based on User Relay", The Journal of The Institute of Internet, Broadcasting and Communication, Vol.17, No.5, pp.25-33, 2017. DOI: https://dx.doi.org/10.7236/JIIBC.2017.17.5.25   DOI
14 S. W. Kang, S. H. Chang, H. J. Kim, S. S. Kim, Y. W. Lee, "A Study on Operating Method to Save Energy from the Adsorption Dryer in the Process of Purifying Compressed Air", Journal of the Society of Korea Industrial and Systems Engineering, Vol.39, No.3, pp.180-191, 2016. DOI: https://dx.doi.org/10.11627/jkise.2016.39.3.180   DOI
15 J. H. Han, J. G. Na, C. B. Kim, "Network Analysis of Technology Convergence on Decentralized Energy by Using Patent Information : Focused on Daegu City Area", Journal of the Society of Korea Industrial and Systems Engineering, Vol.39, No.3, pp.156-169, 2016. DOI: https://dx.doi.org/10.11627/jkise.2016.39.3.156   DOI
16 K. Kim, C. Keum, K. S. Chung, "An Evaluation of the Suitability of Data Mining Algorithms for Smart-Home Intelligent-Service Platforms", Journal of the Society of Korea Industrial and Systems Engineering, Vol.40, No.2, pp.68-77, 2017. DOI: https://dx.doi.org/10.11627/jkise.2017.40.2.068   DOI