An experimental study on the performance of the separate type heat pipe in accordance with the refrigerant charge  

Jeon, Sung-Taek (Devision of Mechanical system Engineering, Incheon University)
Cho, Jin-Pyo (Mechanic.Electron Regional Innovation Center, Incheon University)
Publication Information
Journal of the Korea Academia-Industrial cooperation Society / v.16, no.3, 2015 , pp. 1600-1604 More about this Journal
Abstract
As modern houses are constructed with high-density and high-insulation, there is benefit to reduce energy consumption, but there are many side effects raised from polluted air. To solve the problem, a ventilation system is used to improve a indoor air quality. In this research, we experimentally estimate ventilation performance of HRV(heat recovery ventilator) with heat-pipe according to working fluid filling quantity and ventilation. Heat-pipe used in this study was designated separately to be applied to a ventilation system. The working fluid was R22, which was filled from 40 to 55 (%vol.) by 5(%vol.). Ventilation based on the front velocity was measured from 0.3 m/s to 1.5 m/s by 0.3 m/s intervals. Refrigerant filling quantity with the highest efficiency was found to depend on the ventilation. From this study the optimal refrigerant filling quantity in accordance with the ventilation of the detachable heat pipes was found experimentally.
Keywords
Condenser section; Evaporator Section; Refrigerant charging amount; Separate type heat pipe; Ventilation system;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Lee, W.H., Kim, Y.B., Kim, J.H., and Kim, J.S., "Influence of Working Fluids to Heat Transfer Characteristics of the Heat Exchanger using Oscillating Capillary Tube Heat Pipe for Low Temperature Waste Heat Recovery", Korean Journal of SAREK, Vol. 12 No.7, pp. 659-666, 2000.
2 Gu, Y. U., Kwon, Y. H., Kim, J. S., "An experiment of Pulsating Heat pipe according to the Number of inner flow channel of Flat Tube Heat Exchanger", Proceedings of the SAREK 2013 Winter Annual Conference, pp. 073-076, 2013.
3 Lee, K, W "Seperate heat pipe heat exchanger" Proceedings of the SAREK 1997 Annual Conference, 31-49, 1997.
4 ANSI/ASHRAE Standard 37, "Standard measurement guide, engineering analysis of experimental data", ASHRAE., 2005.
5 Korea Air Cleaning Association, "Indoor environmental professional development training materials", pp 3-9, 2005.
6 Ministry of Environment, "Installation of ventilation equipment, such as a multi-use facility setting research standards", pp 203-204. 2008.