Verifying the Suitability or Unsuitability of the Opening Force Criteria Applied to Air Pressurized Access Door to a Smoke Control Zone  

Lee, Jae-Ou (Department of Fire Safety Engineering, Jeonju University)
Choi, Chung-Seog (Department of Fire Safety Engineering, Jeonju University)
Publication Information
Journal of the Korea Academia-Industrial cooperation Society / v.15, no.9, 2014 , pp. 5820-5825 More about this Journal
Abstract
The aim of this study was to verify the suitability or unsuitability of Korean body types by measuring the opening force criteria of an air pressurized access door to a smoke control zone. The opening force criteria were verified by comparing the NFSC 501A, NFPA 92A and BS-EN 12101-6 based on the body standards information from the Korean Agency for Technology and Standards. When measuring the opening forces, the posture of the body should be standing upright and pushing an access door with the right hand, which is a criterion for designing doors. As a result of analyzing the actual measurement results, the pushing force of men and women in their 30's was the maximum value and the forces in those in their 60's was the minimum value. In addition, the deviations in the pushing forces varied considerably. As a result of comparing the NFSC 501A, the men showed lower values than the criteria in every gender and age variable except for the 20's, 30's and 50's variable. A comparison of the criteria of NFPA 92A showed that the mean of the measured values from every gender and age was also lower than the criteria. In addition, when comparing the criteria of BS-EN 12101-6, it was found that the men in every age variable were higher than the criteria. On the other hand, the women in every age variable were lower than the criteria. Therefore, considering the Korean body type against the Western body type, it was decided that the opening force of an access door to a smoke control area to make a downward adjustment should be 110 N in the local criteria. Furthermore, the criteria should consider the characteristics of buildings and users because an optional application of the international standard is not necessarily suitable for local situations.
Keywords
Differential pressure; Door Closer; Opening force; Optimum design; Smoke control zone;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 J. O. Lee, C. S. Choi, "Study on the Analysis of Differential Pressure of the Access Door for a Smoke Control Zone and the Effectiveness of the Measurement Criteria of its Opening Force", Journal of Korean Institute of Fire Science & Engineering, Vol. 26, No. 04, pp. 24-30, 2012. DOI: http://dx.doi.org/10.7731/KIFSE.2012.26.4.024   과학기술학회마을   DOI
2 J. O. Lee, C. S. Choi, "Study on the Assessment of the Criteria on a Door Closer for the Optimum Design of the Access Door of a Smoke Control Zone", Journal of Korean Institute of Fire Science & Engineering, Vol. 27 No. 03, pp. 66-71, 2013. DOI: http://dx.doi.org/10.7731/KIFSE.2013.27.3.066   과학기술학회마을   DOI
3 SFPE, "SFPE Handbook of Fire Protection Engineerng", Third Edition, Section 4, Chapter 12 Smoke Control, Chapter 13 Smoke Management in Covered Malls and Atria, pp. 274-310, 2002.
4 Dougal Drysdale, "An Introduction to Fire Dynamics", Second Edition, Chapter 11, The Production and movement of smoke, pp. 386-401, 2002.
5 NEMA, National Fire Safety Code, "NFSC 501A of stair cases of specific fire escape stairs and smoke control systems of ancillary rooms", Administrator at National Emergency Management Agency, 2012.
6 Korea Fire Safety Association, "Fire Technician-job training", 2013.
7 Korean Industrial Standard, "KS F 2806 Test methods or checking floor-hinges and door-closers method", Korean Standards Association, 2005.
8 NFPA 92A, "Standard for smoke-control system utilizing barriers and pressure differences", 2009.
9 BS EN 12101-6, "Smoke and heat control systems", Specification for pressure differential systems, 2005.
10 Ministry of Industry usual, "Human Dimensions Research", 2010.
11 Korean Industrial Standard, "KS F 4505 Door closer", Korean Standards Association, 2005.