Abstract
Evacuation fire doors were manufactured by applying phosphorescent paint to the whole fire door whose performance was already recognized, and applying heat sensitive paint around the grip. The facility was improved by the evacuation and safety functions on the fire door, which has been used as only a fire facility, and the fire door is also used as an evacuation facility. The brilliance of the evacuation safety fire door manufactured in this study passed the brilliance test of Korea Fire Institute with a performance more than the brilliance (7mcd after 60 minutes) of the existing inducement sign. During a fire, the visible area is larger than the evacuation door inducement, etc. and light preventive status in the lower part of the fire door was observed during the descent of smoke. Therefore, it is considered to extend the evacuation effective time of evacuators. In heat sensitive paint applied around the grip, a color change is observed on the fire door when approaching a certain temperature ($70^{\circ}C$). Therefore, the first disaster that evacuators can encounter on the grip of a fire door during a fire can be prevented and should be helpful in recognizing the backfiring possibility and preventing safety accidents for firefighters who must enter a fire space.
Keywords
Evacuation Fire Door; Heat Sensitive Paint; Phosphorescent Paint;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Eun-Sun Baek, Geon-Jong Baek, Hoon Shin, Min-Jeong Song, Chan Kook, Sun-Woo Kim, "A study on the awareness of fire safety and evacuation guide system" Journal of korean institute of fir science & engineering., Vol. 24, No. 6, pp45-53, 2010.
2 Wook-Jung Na, Gyu-Yeob Jeon, Won-Hwa Hong, "A study on Comparison with Evacuation Performance according to the type of Egress Induction Equipment" Fall Conference of the KIAEBS., P.249-252, 2007.
3 Myoung-Sin Ahn, "A study of the improvement methodology of the performance and the maintenance efficiency of the management of exit light" P.87, University of Seoul, 2008.
4 Jae-Cheol Lee, "Analysis of the cause of fire and fire safety service for Multiple complex", P.75, Kyungli University, 2010.
5 Man-Sung Hur, Akihiro Fujita, Bitosho, "A Study about the Evacuation Guidance that Used Phosphorescent Material for Stairs" Journal of korean institute of fir science & engineering., Vol. 22, No. 1, pp29-36, 2008.
6 Jeong-Soo Lee, Heung-Soon Kwon, "Evacuation Behaviors under the Corridor and Stair Width Variations in Evacuation Experiments" Journal of the Korea Academia-Industrial cooperation Society Vol. 13, No. 5 pp. 2374-2381, 2012. DOI: http://dx.doi.org/10.5762/KAIS.2012.13.5.2374   과학기술학회마을   DOI
7 National Emergency Management Agency, "Status of fire statistics" 2012.