Abstract
In this study, performance characteristics of a water source heat pump system using $CO_2$ as a refrigerant are investigated experimentally. Cooling and heating capacities and COP of the system are analyzed for various system performance variables such as refrigerant charge, expansion valve opening, compressor frequency and internal heat exchanger. Results show that optimum amount of refrigerant charge and expansion valve opening exists at maximum point of COP curve, and cooling capacity increases but COP decreases with the increase of compressor frequency. When the internal heat exchanger is installed, cooling capacity increases about 4.0% whereas heating capacity decreases about 0.89% compared to the case without internal heat exchanger.
Keywords
Carbon Dioxide; Water Heat Source Heat Pump; Performance Characteristics;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Bivens, D. B., Allgood, C. C., Shiflett, M. B., Patron, D. M., Chisolm, T. C., Shealy, G. S., Yokozeki, A., Wells, W. D. and Geiger, K. A., 1994, HCFC-22 alternative for air conditioners and heat pumps, ASHRAE Transactions, Vol. 100, Part 2, pp. 566-572.
2 Neksa, P., Rekstad, H., Zakeri, G.R. Schiefloe, P.A., 1998, $CO_2$-heat pump water heater: characteristics, system design and experimental results, Int. J. Refrigeration, Vol. 21, No. 3, pp. 172-179.   DOI
3 Liao, S.M., Zhao, T.S. Jakobsen, A., 2000, A correlation of optimal heat rejection pressures in transcritical carbon dioxide cycles, Applied Thermal Engineering, Vol. 20, pp. 831-841.   DOI
4 K. Sato, K. Matsumoto, H. Yamaski, 2002, The development of carbon dioxide hermetic compressor for heat pump water heater systems, Refrigeration, Vol. 77, No. 893, pp. 193-197.
5 Lorentzen, G. Pettersen, J., 1993, A new, efficient and environmentally benign system for car air-conditioning, Int. J. Refrig., Vol. 16, No. 1, pp. 4-12.   DOI
6 Cho, H. H., Ryu, C. G. and Kim, Y. C., 2005, Experimental Study on the Cooling Performance of a Variable Speed $CO_2$ Cycle with Internal Heat Exchanger and Electronic Expansion Valve, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 3, pp. 209-215.   과학기술학회마을
7 McLinden, M. O., Klein, S. A., Lemmon, E. W. Peskin, A. P. 1998, NIST Thermodynamic and Transport Properties of Refrigerants and Refrigerant Mixtures Database(REFPROP), Version 6.0, National Institute of Standards and Technology, Gaithersurg, Maryland, USA.
8 Lorentzen G., 1994, Revival of carbon dioxide as a refrigerant., Int. J. Refrigeration, Vol. 17, No. 5, pp. 292-301.   DOI
9 Lee, E. C., Baek, C. H., Kang, H., Kim, Y. C., Cho, H. H. and Cho, S. W., 2009, Experimental Study on the Performance of a $CO_2$ Heat Pump Water Heater, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 21, No. 6, pp. 367-372.   과학기술학회마을
10 Chen, Y., Gu, J., 2005, The Optimum High Pressure for $CO_2$ Transcritical Refrigeration System with Internal Heat Exchanger, Int. Journal of Refrigeration, Vol. 28, No. 8, pp 1238-1249.   DOI
11 Neksa, P., Rekstad, H., Zakeri, R., Schiefloe, P., 1998, $CO_2$-heat pump water heater: characteristics, system design and experimental results, Int. Journal of Refrigeration, Vol. 21(3). pp. 172-179.   DOI
12 Cho, H. H., Ryu, C. G., Lee, H. S. and Kim, Y. C., 2005, Experimental Study on the Variation of the Optimal Charge with cycle option in the $CO_2$ Refrigeration, Proceedings of the SAREK, pp. 398-403.   과학기술학회마을