Abstract
The purpose of this study is to propose an enhanced variable-speed control method of ground-water circulation pumps using inlet and outlet ground-water temperature difference and analyze its effect for the ground source multi-heat pump system installed in a single-family house. As a result, it has shown to significantly reduce the electricity use of ground-water circulation pump and improve overall system Coefficient of Performance (COP) due to the proposed variable-speed control under partial load conditions after oversized and inefficient single-speed pump retrofit.
Keywords
Ground-Source Heat Pump System; Circulation Pump; Inlet and Outlet Water Temperature Difference; Variable Speed Control;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 Song, S., 2011, Whole Building Performance Evaluation of An All-electrified house integrated with ground-source heat pump system, Proceedings of International Conference on Air-Conditioning and Refrigeration 2011 (ICACR 2011).
2 Choi, J. M., Lim, H. J., Kang, S. H., Moon, J., and Kim, R. H., 2009, Daily Heating Performance of a Ground Source Multi-heat pump at Heating Mode, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 21, No. 9, pp. 527-534.   과학기술학회마을
3 Ahn, B. C. and Kim, J. W., 2010, An Experimental Study on the Cooling Operation Characteristics for Different Entering Water Temperatures in Geothermal Heat Pump System, Transactions of the Korea Society of Geothermal Energy Engineers, Vol. 6, No. 1, pp. 1-7.   과학기술학회마을
4 Kong, H. J., Kang, S. J., Yun, K. S., and Lim, H. J., 2013, An Experimental Study on the Cooling and Heating Performance of a Residential Ground Source Heat Pump System, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 25, No. 3, pp. 156-163.   과학기술학회마을   DOI   ScienceOn
5 Song, J. Y. and Ahn, B. C., 2011, Control Characteristics with Flow Rate Control Methods in Central Heating System, Transactions of the Korea Society of Geothermal Energy engineers, Vol. 7, No. 1, pp. 32-37.   과학기술학회마을
6 Song, S., 2012, An Experimental Study on Variable-speed Control of a Ground-water Circulation Pump Using Inlet and outlet Water Temperature Differeence, Proceedings of the SAREK 2012 Summer Annual Conference, pp. 179-182.