Energy Consumption Analysis based on Filter Differential Pressure when Adopting an Air-side Economizer System for a Data Center  

Park, Seonghyun (Department of Architectural Engineering, Graduate School, Chosun University)
Seo, Janghoo (School of Architecture, Kookmin University)
Jung, Yong-Ho (Department of Architectural Environment, Chungwoon University)
Chang, Hyun-Jae (Department of Architectural Engineering, Hongik University)
Hwang, Seok-Ho (Division of Architecture, Kyungnam University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.25, no.7, 2013 , pp. 371-376 More about this Journal
Abstract
Recently, many studies related to reducing the energy consumption in data centers have been conducted. These studies have mainly focused on the air intake and exhaust system of a computer room air handling unit (CRAH) in the server room, diffuser type, suppression and discharge of the heat generated from the server, and the air-side economizer system. In this study, the energy consumption of the conventional central chilled water cooling system is compared with the energy consumption of the air-side economizer system. We also examined how changes of differential pressure by each filter have influenced energy consumption, using the power usage effectiveness (PUE). Results show that the PUE was improved, and energy consumption decreased, by applying the air-side economizer system.
Keywords
Data center; Air-side economizer system; Filter differential pressure; TRNSYS;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Cho, J. K. and Kim, B. S., 2011, Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers, Energy and Building, Vol. 43, No. 9, pp. 2145-2155.   DOI   ScienceOn
2 ASHRAE, 2009, Particulate and Gaseous Contamination in Datacom Environments, Vol. 8.
3 Kwak, R. Y., Won, G. H., Jung, K. W., and Hug, J. H., 2004, Evaluation of energy saving and development of energy management system of AHU's fan by air filter differential pressure in building, Journal of the Architectural Institute of Korea, Vol. 20, No. 5, pp. 209-216.
4 TRNSYS 17(Transient System Simulation Program), 2011, Solar Energy Lab, Rep., University of Wisconsin- Madison.
5 The Green Grid, 2009, Usage and Public Reporting Guidelines for the Green Grid's Infrastructure Metrics (PUE/DCiE).
6 Ibrahim, M., Bhopte, S., Sammakia, B., Murray, B., Iyenger, M., and Schmidt, R., 2012, Effect of Transient Boundary Conditions and Detailed Thermal Modeling of Data Center Rooms, Packaging and Manufacturing Technology, Vol. 2, No. 2, pp. 300-310.   DOI   ScienceOn
7 Fakhim, B., Behnia, M., Armfield, S. W., and Srinarayana, N., 2011, Cooling solutions in an operational data centre : A case study, Vol. 31, No. 14/15, pp. 2279-2291.   DOI   ScienceOn