Server Room Temperature Condition in Data Center with Cold Aisle Containment System  

Jung, Yong-Ho (Department of Building Equipment and Fire Protection System, Chungwoon University)
Chang, Hyun-Jae (Department of Architectural Engineering, Hongik University)
Seo, Jang-Hoo (Department of Architecture, Chosun University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.25, no.2, 2013 , pp. 79-84 More about this Journal
Abstract
In this study, a cold aisle containment system was proposed among various strategies to reduce the energy waste by recirculation air from the hot aisle. To verify the effectiveness of the cold aisle containment system, a test bed which is similar to an actually existing server room was set up in the Internet Data Center(IDC) building. Comparative experiments, conventional open type cooling system and cold aisle containment system were carried out under actual conditions. The result revealed that the range of inlet temperature of the server system was $20{\sim}25^{\circ}C$ in an existing cooling system and the range of inlet temperature dropped below $20^{\circ}C$ by the cold aisle containment system. After all, cold aisle containment system was proved to be the solution for energy saving cooling system.
Keywords
Cold aisle containment system; Recirculation air; Inlet temperature; Energy saving;
Citations & Related Records
연도 인용수 순위
  • Reference
1 ASHRAE, 2012, High density data centers case studies and best practices, Datacom series, Vol. 7, pp. 26-28.
2 Cho, J. K., 2008, The Planning and Design of the Optimal Cooling System for IT Environments in (Internet) Data Centers, Journal of the Architectural Institute of Korea, Vol. 24, No. 12, pp. 313-320.   과학기술학회마을
3 ASHRAE, 2009, Design considerations for datacom equipment centers second edition, Datacom series, Vol. 3, pp. 82-96.
4 Chang, H. J., Jung, Y. H., and Seo, J. H., 2012, Analysis of Cooling Energy Saving by Cold Aisle Containment System in Internet Data Center Server Room, Journal of Korean Institute of Architectural Sustainable Environment and Building Systems, Vol. 6, No. 3, pp. 181-190.
5 ASHRAE, 2005, Transactions, Vol. 111, No. 2.