Browse > Article
http://dx.doi.org/10.6110/KJACR.2012.24.4.289

Study on the Performance of an ATES Geothermal Heat Pump System and Economic Analysis  

Oh, Myung-Suk (Department of Mechanical Engineering, Hanbat National University)
Choi, Jong-Min (Department of Mechanical Engineering, Hanbat National University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.24, no.4, 2012 , pp. 289-296 More about this Journal
Abstract
The aim of this study is to investigate the performance of a heating and cooling system with aquifer thermal energy storage(ATES heat pump system) known as one of the underground thermal energy storage application systems. The ATES system was composed of heat pump unit and ATES, which was installed in a factory building located in Anseoung. The system represented very high heating and cooling performance, and showed nearly constant COP at each heating and cooling season due to the stability of EWT. The economic analysis about an ATES system and a conventional system was also executed. The conventional system adopted an air-conditioner in the summer season and a LNG boiler in the winter season. The payback period of the ATES system was estimated by 6.62 years.
Keywords
ATES; GCHP; COP; LCC; Economic evaluation;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Lund, J., Sanner, B., Rybach, L, Curtis R., and Hellstrom, G., 2003, Ground-Source Heat Pumps-A World Overview, Renewable Energy World, pp. 218-227.
2 ASHRAE, 1986, Engineering analysis of experimental data, ASHREAE Guideline2, Atlanta U. S. A.
3 Park, C., 2010, Economic analysis of a ground source heat pump, Journal of KSMT, Vol. 12, No. 4, pp. 93-99.
4 DOE, 2001, Ground-source heat pumps applied to federal facilities-second edition, Federal Energy Management Program, DOE/EE-0245 (PNNL-13534), US Department of Energy.
5 Ozgener, L., Hepbasli, A., and Dincer, I., 2007, A key review on performance improvement aspects of geothermal district heating systems and applications, Renew Sustainable Energy Rev., Vol. 11, pp. 1675-1697.   DOI   ScienceOn
6 Laloui, L., Nuth, M., and Vulliet, L., 2006, Experimental and numerical investigations of the behaviour of a heat exchanger pile, Int. J. for Numerical and Analytical Methods in Geomechanics, Vol. 30, pp. 763-781.   DOI   ScienceOn
7 Hamada, Y., Saitoh, H., Nakamura, M., Kubota, H., and Ochifuji, K., 2007, Field performance of an energy pile system for space heating, Energy and Buildings, Vol. 39, pp. 517-524.   DOI   ScienceOn
8 Tarnawski, V. R., Leong, W. H., Momose, T., and Hamada, Y., 2009, Analysis of ground source heat pumps with horizontal ground heat exchangers for northern Japan, Renewable Energy, Vol. 34, pp. 127-134.   DOI   ScienceOn
9 Hamada, Y., Saitoh, H., Nakamura, M., Kubota, H., and Ochifuji, K., 2007, Field performance of an energy pile system for space heating, Energy and Buildings, Vol. 39, pp. 517-524.   DOI   ScienceOn
10 Yu, H. K., 2008, Development and performance evaluation of ground heat exchanger utilizing PHC pile foundation of building, Journal of the Korean Solar Energy Society, Vol. 5, pp. 56-64.
11 Paksoy, H. O., Gurbuz, Z., Turgut, B., Dikici, D., and Evliya, H., 2004, Aquifer thermal storage( ATES) for air-conditioning of a supermarket in Turkey, Renewable Energy, Vol. 29, pp. 1991-1996.   DOI   ScienceOn
12 NexGeo, 2010, Aquifer thermal energy storage heating and cooling systems development, Final Report of Ministry of Knowledge Economy, 2007-N-GE02-P-01.
13 Ministry of Knowledge Economy, 2008, Standards of support, installation, and management for new and renewable energy system, Ministry of Knowledge Economy Announcement 2008-3.