Abstract
Ground-coupled heat pump (GCHP) systems utilize the immense renewable storage capacity of the ground as a heat source or sink to provide space heating, cooling, and domestic hot water. The main objective of the present study is to investigate the cooling and heating performance of a small scale GCHP system with horizontal ground heat exchanger (HGHE). In order to evaluate the performance, a water-to-air ground-source heat pump unit connected to a test room with a net floor area of 18.4 m2 and a volume of 64.4 m3 in the Korea Institute of Construction Technology ($37^{\circ}39, $126^{\circ}48) was designed and constructed. This GCHP system mainly consisted of slinky-type HGHE with a total length of 400 m, indoor heat pump, and measuring devices. The peak cooling and heating loads of the test room were 5.07 kW and 4.12 kW, respectively. The experimental results were obtained from March 15, 2011 to August 31, 2011 and the performance coefficients of the system were determined from the measured data. The overall seasonal performance factor (SPF) for cooling was 3.31 while the system delivered heating at a daily average performance coefficients of 2.82.
Keywords
Ground-coupled heat pump; Horizontal ground heat exchanger; Cooling and heating; Seasonal performance factor(SPF); COP;
Citations & Related Records
Times Cited By KSCI : 6  (Citation Analysis)
연도 인용수 순위
1 Lee, J. Y., Chung, J. T. Woo, J., and Choi, J. M., 2010, Influence of the secondary fluid glow rate of the performance of a GSHP system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 22, No. 10, pp. 649- 656.
2 Kang, S.-H., Choi, J. M., Moon, J., and Kwon, H., 2010, Heating performance of a ground source multi-heat pump for a greenhouse, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 22, No. 6, pp. 337- 344.   과학기술학회마을
3 Sohn, B. and Choi, H., 2011, Thermal diffusivity evaluation of backfilling materials for horizontal ground heat exchanger using singleprobe method, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 4, pp. 356-364.   DOI
4 IGSHPA, 2009, Ground Source Heat Pump Residential and Light Commercial Design and Installation Guide, Oklahoma State University.
5 Sohn, B., 2011, Evaluation of ground temperature and soil thermal diffusivity using the soil temperature data of KMA, Trans. Korea Society of Geothermal Energy Engineers, Vol. 7, No. 1, pp. 1-9.   과학기술학회마을
6 Kusuda, T. and Achenbach, P. R., 1965, Earth temperature and thermal diffusivity at selected stations in the United States, ASHRAE Transactions, Vol. 71, pp. 61-75.
7 MKE(KNREC), 2010, Guidelines for New and Renewable Energy Systems, Ministry of Knowledge Economy.
8 Kline, S. J., 1985, The purpose of uncertainty analysis, J. Fluids Engineering, Vol. 107, pp. 153-160.   DOI
9 Benli, H. and Durmus, A., 2009, Evaluation of ground-source heat pump combined latent heat storage system performance in greenhouse heating, Energy and Buildings, Vol. 41, pp. 220-228.   DOI   ScienceOn
10 Tarnawski, V. R., Leong, W. H., Momose, T., and Hamada, Y., 2009, Analysis of ground source heat pumps with horizontal ground heat exchangers for northern Japan, Renewable Energy, Vol. 34, pp. 127-134.   DOI   ScienceOn
11 Esen, H., Inalli, M., Esen, M., and Pihtili, K., 2007, Energy and exergy analysis of a groundcoupled heat pump system with two horizontal ground heat exchangers, Building and Environment, Vol. 42, pp. 3606-3615.   DOI   ScienceOn
12 Sohn, B. H., Cho, C. S., Shin, H. J., and An, H. J., 2005, Cooling and heating performance evaluation of a GSHP system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 1, pp. 71-81.   과학기술학회마을
13 Sohn, B., Choi, J. M., and Choi, H., 2011, Performance simulation of ground-coupled heat pump(GHP) system for a detached house, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 6, pp. 392- 399.   과학기술학회마을   DOI
14 Lee, C., Park, M., Min, S., Kang, S.-H., Sohn, B., and Choi, H., 2011, Comparison of effective thermal conductivity in closed-loop vertical ground heat exchangers, Applied Thermal Engineering, Vol. 31, pp. 3669-3676.   DOI   ScienceOn