Performance Variation with Length of Internal Heat Exchanger in CO2 Cooling Cycle Using an Ejector  

Kang, Byun (Graduate School of Mechanical Engineering, Chosun University)
Cho, Hong-Hyun (Department of Mechanical Engineering, Chosun University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.24, no.2, 2012 , pp. 147-154 More about this Journal
Abstract
Recently, many researchers have studied the performance of the transcritical $CO_2$ refrigeration cycle in order to improve the system efficiency. In this study, the length of IHX in the $CO_2$ ejector cycle was varied so as to evaluate the performance improvement. As a result, compressor work and cooling capacity was increased by 3% and 5% as the length of internal heat exchanger was changed from 3 m to 15 m. The best COP was appeared at internal heat exchanger length of 12 m, and it was 3.01. Besides, the length of internal heat exchanger has a big effect to pressure lift ratio and entrainment ratio in the ejector $CO_2$ cycle and it may be changed with operating conditions and system specifications.
Keywords
Carbon dioxide; Transcritical system; Ejector; Internal heat exchanger;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Li, D. and Groll, A., 2005, Transcritical $CO_{2}$ refrigeration cycle with ejector-expansion device, International Journal of Refrigeration, Vol. 28, pp. 766-773.   DOI   ScienceOn
2 Sarkar, J., 2008, Optimization of ejector-expansion transcritical $CO_{2}$ heat pump cycle, Energy, Vol. 33, pp. 1399-1406.   DOI   ScienceOn
3 Ortiz, T. M., Li, D., and Groll, A. E., 2003, Evaluation of the Performance Potential of $CO_{2}$ as a Refrigerant in Air-to-Air Conditioner and Heat Pumps:System Modelling and Analysis, ARTI final report No. 21CR/610- 10030.
4 Gnielinski, V., 1976, New equations for heat and mass transfer in turbulent pipe and channel flow, International Chemical Engineering, Vol. 16, pp. 59-68.
5 Churchill, S. W., 1977, Friction-factor equation span all fluid flow regimes, Chemical Engineering, Vol. 7, pp. 91-92.
6 Yoon, S. H., 2002, Studies on the Characteristics of Evaporation and supercritical Gas Cooling Heat Transfer of Carbon Dioxide, Ph. D. thesis, Seoul University, Seoul, Korea.
7 Wang, C. C., Lee., S. W., and Sheu, W. J., 2001, A Comparative Study of Compact Enhanced Fin-and-Tube Heat Exchanges, International Journal of Heat and Mass Transfer, Vol. 44, pp. 3565-3573.   DOI   ScienceOn
8 ASHRAE, 1983, Methods of testing for seasonal efficiency of unitaty air-conditioner and heat pumps, ASHRAE Standard, p. 116.
9 Kang, B. and Cho, H. H., 2011, Comparison of Performance in $CO_{2}$ Cooling System with an Ejector for Various Operating Condtitions, SA REK, Vol. 23, pp. 505-512.
10 Nakagawa, M., Marasigan, A. R., Matsukawa, T., and Kurashina, A., 2011, Experimental analysis on the effect of internal heat exchanger in transcritical $CO_{2}$ refrigeration cycle with two-phase ejector, International Journal of Refrigeration, Vol. 34, pp. 1577-1586.   DOI   ScienceOn