Numerical analysis has been conducted to investigate the fluid flow and fume mixing ratio characteristics of scattering fume in a push-pull ventilation system and optimally improve the flow patterns of scattering fume in the existing ventilation system. This ventilation system has been simulated by using commercial CFD code. In the case of the existing system, although the air is sprayed from air-curtain to prevent the fume from being scattered in upper hood, the improved air supply hood can remove the fume from the wide area in the high pressure. It is verified that the deeper plating storage is more advantageous. Also, by installing the shied around the plating storage, the scattering of the fume to the atmosphere was prevented effectively by surrounding flux.
Keywords
Zinc plating; Local ventilation; Push hood; Pull hood;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 Kim. B. G., Choi. H. W., Yong. H. T. and Lee. M. H., 2005, Horizontal air-jet effect on the natural convection around a range-hood system, Korean Journal of Air-Conditioning and Refrigeration Engineering Vol. 17, No. 4, pp. 333-340.   과학기술학회마을
2 Lim. K. B., Lee. K. S. and Lee. C. H., 2006, A numerical study on the characteristics of flow field, temperature and concentration distribution according to changing the shape of separation plate of kitchen hood system, Transactions of the KSME B, Vol. 30, No. 2, pp. 177-185.   과학기술학회마을
3 Witt, P. J., Solnorda, C. G., Mittoni, L. J., Finn, S. and Pluta, J., 2006, Optimising the design of fume extraction hoods using a combination of engineering and CFD modelling, Applied Mathematical Modelling, Vol. 30, pp. 1167-1179.   DOI   ScienceOn
4 Yi, C. S., Jang, S. C. and Choi, J. H., 2009, Numerical Analysis on Hood Shape Improvement of Local Ventilation System, Korean Journal of Air-Conditioning and Refrigeration Engineering Vol. 21, No. 4, pp. 260-265   과학기술학회마을
5 Lee. S. S., Moon. J. H., Lee. T. G., Lim. Y. C. and Lee. J. H., 2004, Improvement of working environment by the space ventilation system in a large welding factory, SAREK winter conference, pp. 345-350.
6 Lim. K. B., Lee. K. S. and Lee. C. H., 2006, A numerical study on the flow characteristics of kitchen hood system, Korean Journal of Air- Conditioning and Refrigeration Engineering Vol. 18, No. 4 pp. 359-369.   과학기술학회마을
7 Koo, N. Y., Lee. Y. K. and Young. Y. S., 2002, An experimental study on the air curtain range hood interrupting the diffusion of polluted air, SAREK winter conference, pp. 382-387.