Browse > Article

A Study on the Prediction of Indoor Environment in Bio Safety Level 3 Laboratory According to Biohazard Scenario  

Park, Hyun-Jin (Graduate School, Kyungwon University)
Hong, Jin-Kwan (Department of Building Equipment and System Eng, Kyungwon University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.22, no.11, 2010 , pp. 745-750 More about this Journal
Abstract
Since the implementation of the LMO Law in Korea, the importance of the design qualification of BSL3 lab. is emphasizing. In this study, multizone simulation for three kind of biohazard scenarios using CONTAM is performed for design qualification of BSL3 lab. Also, in the case of unexpected spread of contaminants such as Influenza A virus(H1N1) in BL3 zone, the design qualification is carried out for diffusion and decontamination of contaminants according to differential pressure of BSL3 anteroom and door area of BSL3 lab. Also, in this study, appropriateness of laboratory room differential pressure and air flow rate to maintain pressure difference between laboratory rooms, and energy consumption due to air change rate variation according to door area in BL3 lab. Simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.
Keywords
BSL3: Biosafety level 3 lab.; Biohazard scenario; Influenza A: H1N1; Multizone simulation; Energy consumption;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Hong, J. K., 2010, A Case Study on the Validation of BL3 Laboratory and Engineering Cost Evaluation of BL3 Laboratory, Design, Construction and Validation Workshop of BL3 Laboratory, pp. 229-253.
2 Hong, J. K., 2010, Design Simulation for BL3 Laboratory, Design, Construction and Validation Workshop of BL3 Laboratory, pp. 61-87.
3 National Technical Information Service U.S. Department of Commerce Springfield, VA 22161.
4 ASHRAE Handbook, 1997, American Society Heating, Refrigerating and Air-Conditioning Engineers. Inc, Atlanta, GA. Chapter, Vol. 25, p. 18.
5 Walton, G. N., 2005, CONTAM2.4 User Guide and Program Documentation, NISTIR, Vol. 7251, p. 215.
6 Lee, H. W., Choi, S. G. and Hong, J. K., 2009, A Study on Verification for the Design of Bio Safety Level 3 Laboratory by using Multi-zone Simulation, Journal of SAREK, Vol. 21, No. 12, pp. 671-677.   과학기술학회마을
7 ARS Manual-242 2002, Facilities Design Standards, pp. 180-181.
8 Korea Center for Disease Control and Prevention, According to between nations transfer of living Modified Organisms etc of Law, 2008.