Browse > Article

Analytical Study on the Performance of Fuel Cell Driven Ground Source Heat Pump Heating and Cooling System of a Large Community Building  

Byun, Jae-Ki (Graduate School of Mechanical Engineering, Korea University)
Jeong, Dong-Hwa (Graduate School of Mechanical Engineering, Korea University)
Choi, Young-Dong (Department of Mechanical Engineering, Korea University)
Cho, Sung-Hwan (Department of Mechanical and Automotive Engineering, Jeonju University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.21, no.6, 2009 , pp. 355-366 More about this Journal
Abstract
In the present study, fuel cell driven ground source heat pump system is applied to a large community building and performance of the heat pump system is computationally analyzed. Conduction heat transfer between brine pipe and ground is analyzed by TEACH code to predict the performance of heat pump system. Predicted COP of the heat pump system and the energy cost were compared with variation of the location of the objective building the water saturation rate of soil and the driven powers of heat pump system. Significant reduction of energy cost can be accomplished by employing the fuel cell driven heat pump system in comparison with the late-night electricity driven system. It is due to the low electricity production cost of fuel cell system and the application of recovered waste heat generated during electricity production process to the heating of large community building.
Keywords
Ground Source; Fuel Cell; Heat Pump;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 ASHRAE HANDBOOK, 1993, Fundamentals, pp. 27-28
2 Choi, Y. D., 2004, Study on the application of heat pump heating and cooling systems to resident and medical buildings, Ministy of Commerce, Industry and Energy, pp. 107-109
3 Lee, J. H., Choi, Y. D. and Cho, S. H., 1999, A comparison on simulation results of load an-alysis program, Proceeding of the SAREK, pp. 51-64
4 Choi, Y. D., Han, S. H., Cho, S. H., Kim, D. S., Um, C. J., 2008, Study on the simulation of heating and cooling system to resident building, Korea Journal of Air-Conditioning and Refrigeration Engineering, Vol. 20, No. 1, pp. 65-74
5 Tromble, A., Serres, L., 1994, Air-earth exchanger study in real site experimentation and simulation, Energy and Building, Vol. 21, pp. 155-162   DOI   ScienceOn
6 Lee, C. S. and Choi, Y. D., 1997, Analysis of energy consumption of office building by thermal resistance-capacitance method, Korea Journal of Air-Conditioning and Refrigeration Engineering, Vol. 9, No. 1, pp. 1-13
7 Patankar, S. V., 1980, Numerical Heat Transfer and Fluid Dynamics for Engineers, A. Publication of Engineering Education System
8 TRSYS, 1994, RTNSYS reference manual, Univ. of Wisconsin-Madison Solar energy lab
9 Jeong, D. H., Byun, J. K., Choi, Y. D., and Cho, S. H., 2008, Study on the Performance of Fuel Cell Driven Compound Source Heat Pump System to a Large Community Building, New and Renewable Energy, Vol. 4, No. 3, pp. 23-35   과학기술학회마을   ScienceOn
10 Krati, M. and Kreinder, J. F., 1989, Analytical model for heat transfer in an under ground air turnnel, Solar Engineering ASME, Vol. 2, pp. 878-888
11 ASHRAE HANDBOOK, 1993, Fundamentals, pp. 9-11
12 BLAST, 1998, BLAST simulation program reference manual, Univ. of Illinois
13 Choi, Y. D., An, J. S., Kim, W. K., Pak, H. S. and Jang, M. S., 1996, Analysis on the thermal performances of cool tube systems for one year, Proceedings of the KSME 1996 Fall Annual Meeting, pp. 725-731
14 Yoon, J. H., Hong, J. K., Lee, N. H. and Choi, Y. D., 1993, Simulation of thermal performance of model hot water panel house in consideration of radiant heat transfer, Korea Journal of Air-Conditioning and Refrigeration Engineering, Vol. 5, No. 4, pp. 295-305