This paper presents the effects of thermoelectric module arrangement on the cooling performance of an air conditioner using thermoelectric module. A prototype of air cooling system, employing several thermoelectric modules, has been designed and built. The evaporative cooling technique is adopted for hot side of the module. The number of thermoelectric module in the system has been varied in the range of $2{\sim}8$. The optimal operation conditions, such as input power to the thermoelectric module, fans and pump, have been determined for each arrangement of the system and the cooling performance has been compared under the optimal operation. It is found that both cooling capacity and COP are increased as the number of thermoelectric module increased. It is also found that cooling capacity can be improved by connecting the thermoelectric modules in series than in parallel, while the COP is little affected.
Keywords
COP; Peltier effect; Thermoelectric module; Thermoelectric cooling;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Sofrata, H., 1996, Heat rejection alternatives for thermoelectric refrigerators, Energy Conversion and Management, Vol. 37, No.3, pp. 269-280   DOI   ScienceOn
2 Stockholm, J. G., 1997, Current state of Peltier cooling, 26th Int. Conference of Thermoelectrics, Dresden, Germany
3 Guler, N. F. and Ahiska, R., 2002, Design and testing of a microprocessor-controlled portable thermoelectric medical cooling kit, Applied Thermal Engineering, Vol. 22, pp. 1271-1276   DOI   ScienceOn
4 Hwang, J. and Kang, B. H., 2006, An experimental study on the optimal operation condition of an air-cooler using thermoelectric modules, Korean Journal of Refrigeration and Air Conditioning, Vol. 18, No.1, pp. 66-72   과학기술학회마을
5 Jin, J. H., Cho, J. R. and Kim, M. G., 2002, Study on the performance of showcase refrigerating chamber using thermoelectric module, Proceedings of the SAREK 2002 Winter Annual Conference, pp. 35-40
6 Kang, B. H., Chang, H. J. and Kim, S. Y., 2002, Cooling characteristics at hot side of the thermoelectric module for an air conditioner, Korean Journal of Refrigeration and Air Conditioning, Vol. 14. No.3, pp.214-220
7 Astrain, D., Vian, J. G. and Dominguez, M., 2003, Increase of COP in the thermoelectric refrigeration by the optimization of heat dissipation, Thermal Engineering, Vol. 23, pp. 2183-2200   DOI   ScienceOn