Abstract
A study on frost prevention of fin-tube heat exchanger is experimently performed by spreading antifreezing solution on heat exchanger surface. It is desirable that the antifreezing solution spreads completely on the surface forming thin liquid film to prevent frost nucleation and crystal growth and to reduce the thermal resistance across the liquid film. A small amount of antifreezing solution falls in drops on heat exchanger surface using two types of supplying devices, and a porous layer coating technique is adopted to enhance the wettedness of antifreezing solution on the surface. It is observed that the antifreezing solution liquid film prevents fin-tube heat exchanger from frosting, and heat transfer performance does not degrade through the frosting tests. The concentration of supplied antifreezing solution can be determined by heat transfer analysis of the first row of heat exchanger to avoid antifreezing solution freezing due to dilution by moisture absorption.
Keywords
Antifreezing solution; Frost prevention; Pin-Tube heat exchager; Micro liquid film;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Verbeeck, R. M. H., Thun, H. P. and Verbeek, F., 1976, Refractive index of the propylene glycol-water system from 15 to $50^{\circ}C$, Bull. Soc. Chim. Belg., Vol. 85, No.8, pp. 531-534   DOI
2 Jhee, S. and Lee, K. S., 2000, An experimental study of the surface treatment effect on the frosting/defrosting behavior of a fintube heat exchanger, Transaction of the KSME B, Vol. 24, No.8, pp.1062-1068   과학기술학회마을
3 Cho, H., Kim, Y., Noh, H.-I., Kim, Y. and Park, Y. C., 2002, Experimental study on the performance characteristics of hot-gas bypass and on-off defrosting cycle in a showcase refrigeration system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 14, No.6, pp.493-502   과학기술학회마을
4 Collier, J. G. and Thome, J. R., 1994, Convective Boiling and Condensation, Clarendon Press, p. 445
5 Han, H. D. and Ro, S. T., 1999, Experiment of frost growth on the parallel plates in the condition of laminar and low humidity, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol.11, No.4, pp.440-447   과학기술학회마을
6 Hwang, Y. and Lee, Y., 2002, A frost-less heat pump, Journal of SAREK, Vol. 31, No. 3, pp. 53-58
7 Domanski, P. A., 1989, EVSIM - An evaporator simulation model accounting for refrigerant and one dimensional air distribution, NISTIR 89-4133, U. S. Dept. of Commerce, NIST, Maryland 20899
8 Hayashi, Y., Aoki, A., Adachi, S. and Hori, K., 1977, Study of frost properties correlating with frost formation types, Journal of Heat Transfer, Vol. 99, pp.239-245   DOI
9 Chang, Y.-S. and Yun, W.-N., 2005, An experimental study on the frost prevention using micro liquid film of an antifreezing solution, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No.5, pp, 459-467   과학기술학회마을
10 Lee, K. S., Kim, G. W. and Jhee, S., 1998, An experimental study of behavior defrosting on the fin-tube heat exchanger, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 10, No. 6, pp.649-657   과학기술학회마을
11 Lee, J. W., Lee, D. Y. and Kang, B. H., 2003, An experimental study on the effects of porous layer treatment on evaporation heat transfer from an inclined surface, Proceedings of the SAREK, pp. 153-158