Browse > Article

Experimental Study on Cooling Characteristics of Multi - Air Conditioner using Inverter Scroll Compressor  

권영철 (선문대학교 기계공학과)
고국원 (선문대학교 기계공학과)
진의선 (선문대학교 대학원)
허삼행 (선문대학교 대학원)
전용호 (선문대학교 대학원)
이영덕 (위니아 만도)
박인규 (위니아 만도)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.16, no.4, 2004 , pp. 311-317 More about this Journal
Abstract
In the present study, the cooling characteristics of the multi-air conditioner (A/C) using an inverter scroll compressor are experimentally investigated for the number of the indoor units and the operating conditions (2$0^{\circ}C$, 24$^{\circ}C$, 26$^{\circ}C$) under the cooling standard conditions by KS C 9306. In the case of the simultaneous operation for 3 indoor units, the cooling capacity, the mass flow rate and the input power have a decreasing trend and COP has an increasing trend, with decreasing the difference in the operating temperature of the indoor unit and the room temperature. In the case of the simultaneous operation for 2 indoor units, the COP of the indoor unit with large cooling capacity is high when the operating temperature is high, but the COP of the indoor unit with low cooling capacity is high when the operating temperature is low. In the case of the single operation for one unit, when the large cooling capacity of the indoor unit is less than 50% the compressor operates at the minimum operation frequency region and the COP decreases.
Keywords
Multi-A/C; Inverter; Cooling capacity; COP; Part load; Scroll compressor;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Performance analysis of variable speed scroll compressors for alternative refrigerants /
[ Lee,G.H.;Kim,D.H.;Hwang,Y.K. ] / Proceedings of the SAREK
2 Method of testing for seasonal efficiency of unitary air conditioners and heat pumps /
[ ASHRAE ] / ASHRAE Standard ANSI/ASHRAE 116-1983
3 Sunmoon university air-enthalpy calorimeter performance evaluation project /
[ KTL ] / Final Report
4 Multi air conditioner with two indoor unit /
[ Fujita,Y.;Kubo,T.;Suma,S. ] / Refrigeration
5 A comparative analysis of single alld contlnuously variable-capacity heat pump concepts /
[ Rice,C.K.;Fisher,S.K. ] / Proc. of the DOE/ORNL Heat Pump Conference
6 Performance of the flow distribution and capacity modulation of a multi-heat pump system /
[ Choi,J.M.;Kim,Y.C.;Ha,J.H. ] / Proceedings of the SAREK   과학기술학회마을
7 Air conditioners /
[ KS C 9306 ] / Korean Agency for Technology and Standard
8 Experimental study on performance evaluation of system A/C using PWM or inverter method(Heating characteristics at low temperature conditions) /
[ Kim,D.H.;Jun,Y.H.;Heo,S.H.;Kwon,Y.C.;Moon,J.M.;Hong,J.T. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
9 Experimental study on performance evaluation of system air-conditioning using compressor of PWM or inverter method(Cooling anf heating characteristics) /
[ Jun,Y.H.;Kim,D.H.;Heo,S.H.;Kwon,Y.C.;Moon,J.M.;Hong,J.T. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을