Evaluation of Energy Consumption of HVAC System for Air Filter Pressure Difference Change in Commercial Buildings  

Won Keun-Ho (서울시립대학교 대학원)
Kwak Ro-Yeul (FMTelecom 기술연구소)
Huh Jung-ho (서울시립대학교 건축학부)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.16, no.12, 2004 , pp. 1227-1233 More about this Journal
Abstract
Air handling unit (AHU)'s air filter pressure difference is important for energy consumption and indoor air quality. Both energy Performance data and air filter differential pressure of AHU in real office buildings were monitored and analyzed to investigate quantitatively energy impact as dust buildup level on air filter grows. We also modeled and simulated CAV system using HVACSIM+ program to examine the energy effect of dust buildup on filters. Through analysis of time series pressure drop data, the filter pressure difference rate has been increased due to cumulative supply air flow rate increase. As filter pressure drop increased to 1 inch water column, it is found that the supply air flow rate was decreased by 10%, the chilled water flow rate was increased by 5.9% and the pump energy consumption was increased to 5.9%.
Keywords
AHU; Air filter; Building energy performance; Dynamic simulation; HVACSIM+;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Kim, S. M., 1993, The effect of pressure drop of filter on blowing power in clean rooms, MS thesis, Hanyang University, Seoul, Korea
2 Building Maintenance Handbook, 1994, Ohmsha, Ltd.
3 Liu, M., David, E. and Song, D., 2003, Air filter-associated fan energy consumption in variable air volume systems, ASHRAE Transactions, Vol. 109, Part 1, pp. 45-51
4 Kwak, RY., Won, G. H., jung, K. W. and Huh, J. H., 2004, Evaluation of energy saving and development of energy management system of AHU's fan by air filter differential pressure in building, Journal of the Architectural Institute of Korea, Vol. 20, No.5, pp. 209-21
5 http:;/www2.starcat.ne.jp/%7Enob_naka/jc.htm