Browse > Article

The Performance of a Heat Pump with a Variation of Expansion Valve at Various Charging Conditions  

최종민 (고려대학교 차세대기계설계연구소)
김용찬 (고려대학교 기계공학과)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.8, 2003 , pp. 661-666 More about this Journal
Abstract
Constant area expansion devices such as capillary tubes, short tube orifices are being gradually replaced with electronic expansion valves (EEVs) because of increasing focus on comfort and energy conservation. In this study, the performance of a water-to-water heat pump as a function of refrigerant charge is investigated in steady state, cooling mode operation with expansion devices of a capillary tube and an EEV. The performance of the capillary tube system varies drastically according to the change of refrigerant charge amount and inlet temperature of the secondary fluid in the condenser. Cooling capacity and COP of the EEV system show little dependence on the refrigerant charge, while those are strongly dependent on the secondary fluid temperature at the condenser inlet. In general, for a wide range of operating conditions the EEV system shows much higher performance as compared with the capillary tube system. The performance of the EEV system can be optimized by adjusting EEV opening to maintain a constant superheat at all test conditions.
Keywords
Charge; Heat pump; Capacity; Superheat; Subcooling;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Standard for water-source heat pumps /
[ ARI ] / ARI Standard 320
2 Methods of testing for rating water-cooled refrigerant condensers /
[ ASHRAE ] / ASH-RAE Standard 22
3 Influence of the expansion device on the seasonal energy requirements of a residential air conditioner /
[ Stoecker,W.F.;Smith Ⅲ,L.D.;Emde,B.N. ] / ASHRAE Trans.
4 The effects of the refrigerant charge on the performance of an air conditioner with capillary tube expansions /
[ Choi,E.;Kim,J. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
5 A research into a new method of refrigeration charging and the effects of improper charging /
[ Houcek,J.;Thedford,M. ] / Proceedings of 1st Annual Sym. on Efficient Utilization of Energy in Residential and Commercial Buildings
6 Optimal control of electronic systems requires fast reacting expansion valves and new controller design /
[ Schmidt,F. ] / Proceedings, The 20th International Congress of Refrigeration IIR/IIF
7 The effect of improper refrigerant charging on the performance of a residential heat pump with fixed expansion devices (Capillary Tube and Short Tube Orifice) /
[ Farzard,M.;O'Neal,D.L. ] / Proceedings, The 29th Intersociety Energy-Conversion Engineering Conference