Browse > Article

A Numerical Study on the Design of a Grease Filter for Kitchen Ventilation  

김기정 (한국과학기술연구원 열유동제어연구센터)
배귀남 (한국과학기술연구원 대기자원연구센터)
김영일 (한국과학기술연구원 열유동제어연구센터)
허남건 (서강대학교 기계공학과)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.8, 2003 , pp. 619-629 More about this Journal
Abstract
A grease filter is used to remove grease generated from a cooking appliance in a kitchen. Since the inertial impaction is a dominant particle removal mechanism of the grease filter, the performance of the filter is greatly affected by the geometry. This numerical study has been conducted to investigate the effect of geometry on the performance of grease filters for four models having nominal flowrate of 100 m$^3$/h. Four models were designed by changing the shape of impaction surface, the length of eyelid, and the number of eyelids of the grease filter. The flow field and particle trajectories in the grease filter with a flow chamber were simulated using the commercial code of STAR-CD. The difference of air velocity and pressure distributions among four models was discussed in detail. The collection efficiency curves and the pressure drops of four models were also compared. It was found that the grease filter model with flat top surfaces shows highest performance among four models, having high particle collection efficiency and relatively low pressure drop. The cutoff diameter of this model representing 50-% collection efficiency is about 7.1 ${\mu}{\textrm}{m}$ for water droplets at 100 m$^3$/h.
Keywords
Grease filter; Particle; Collection efficiency; Pressure drop; Geometry; Kitchen ventilation;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 /
[ Hinds,W.C. ] / Aerosol Technology
2 Effect of ultra-Stockesian drag and particle interception on impaction characteristics /
[ Rader,D.J.;Marple,V.A. ] / Aerosol Science and Technology   ScienceOn
3 Prediction of the ventilation performance in a kitchen with various locations of gas range and window /
[ Kim,K.H.;Lee,J.H.;Park,M.S.;Lee,D.W. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
4 Performance investigation of a grease filter for kitchen ventilation in an apartment house /
[ Bae,G.N.;Kim,K.J.;Kim,Y.I. ] / Proceedings of the SAREK 2001 Summer Annual Conference
5 Gravimetric and Dust-Spot Procedures for Testing Air-Cleaning Devices Used in General Ventilation for Removing Particulate Matter /
[ ASHRAE ] / ANSI/ASHRAE 52.1~1992
6 A numerical study on the particle collection characteristics of a grease filter for kitchen ventilation /
[ Kim,K.J.;Bae,G.N.;Kim,Y.;Hur,N. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
7 Effect of make up air configuration on kitchen exhaust system performance /
[ Jung,H.;Han,H. ] / Proceedings of the SAREK 2000 Winter Annual Conference
8 Performance prediction of a viscous metal filter /
[ Bae,G.N.;Park,S.H.;Ji,J.H.;Hwang,J.H. ] / Proceedings of the SAREK 2000 Winter Annual Conference
9 /
[ Computational Dynamics Limited ] / Methodology(STAR-CD version 3.10A)