Browse > Article

Analysis of the Condenser Performance Installed in the Air-Conditioning Plant Room of a High-Rise Building  

최석호 (한양대학교 대학원)
이관수 (한양대학교 기계공학부)
김병순 (LG전자㈜)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.7, 2003 , pp. 586-594 More about this Journal
Abstract
The performance of the condenser installed in the air-conditioning plant room of a high-rise building was studied numerically. The effect of the draft direction on the performance of an air-conditioner was analyzed. The on-coil temperature of the condenser was investigated by varying the arrangement and location o( the condenser in the air-conditioning plant room. The performance of an air-conditioner was also evaluated by using COP (coefficient of performance) and CGPI (condenser group performance indicator). The condenser in an air-conditioning plant room should be arranged in such a manner that the fan of the condenser is facing the outside of the building to exhaust the hot air directly, The model by which the condenser is located at the lower-left end of an air-conditioning plant room can prevent the hot air from reentering, and allow indrafting of fresh air. When the direction of draft is to the frontal face of the building, the performance of the condenser above 30th floor is degraded.
Keywords
Condenser; Air-conditioning plant room; Draft; COP; Arrangement of condenser; High-rise building;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Flow analysis of condenser cooling air delivery via building light well /
[ Chow,T.T.;Lin,Z.;Wang,Q.W. ] / Applied Thermal Engineering   ScienceOn
2 Influence of a depth of recessed space to flow due to air-conditioner heat rejection /
[ Bojic,M.;Lee,M.;Yik,F. ] / Energy and Buildings   ScienceOn
3 Numerical study on diffusion field as affected by arrangement of supply and exhaust openings in conventional flow type clean room /
[ Murakami,S.;Kato,S. ] / ASHRAE Transactions
4 /
[ Patankar,S.V. ] / Numerical Heat Transfer and Fluid Flow
5 Influence of clearances on the energy performance of window-type air-conditioners at the same level outside residential buildings /
[ Bojic,M.;Lee,M.;Yik,F.;Burnett,J. ] / Building and Environment   ScienceOn
6 /
[ Fluent Inc. ] / Fluent Version 5.0 User Manual
7 Effect of Building re-entrant shape on performance of air-cooled condensing unitsl /
[ Chow,T.T;Lin,Z.;Wang,Q.W. ] / Energy and Buildings   ScienceOn
8 Prediction of on-coil temperature of condensers installed at tall building re-entrant /
[ Chow,T.T.;Lin,Z. ] / Applied Thermal Engineering   ScienceOn
9 Efficiency of transient contaminant removal from a slot ventilated enclosure /
[ Lage,J.L.;Bejan,A.;Anderson,R. ] / Int. J. Heat Mass Transfer   ScienceOn
10 Effect of geometric parameters on ventilation performance in a dry room /
[ Lee,K.S.;Choi,S.H. ] / Drying Technology
11 Numerical and experimental study on turbulent diffusion fields in conventional flow type clean room /
[ Murakami,S.;Kato,S.;Suyama,Y. ] / ASHRAE Transactions