Experimental Study on Performance Evaluation of System A/C using PWM or Inverter Method (Heating Characteristics at Low Temperature Conditions)  

김대훈 (선문대학교 기계공학과)
전용호 (선문대학교 기계공학과)
권영철 (선문대학교 기계공학과)
이윤수 (센추리 기술연구소)
문제명 (삼성전자 시스템가전사업부)
홍주태 (삼성전자 시스템가전사업부)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.7, 2003 , pp. 551-556 More about this Journal
Abstract
The present study concerns an experiment on the heating characteristics of a system air-conditioner (A/C) using PWM method or inverter method at low temperature con-ditions. The compressors used are digital scroll type and BLDC inverter type. Under the low outside temperature condition, -5$^{\circ}C$, -1$0^{\circ}C$, -15$^{\circ}C$, heating capacities and COPs are mea-sured by the psychometric calorimeter using air enthalpy method. Also, outlet air temperatures at heating operation mode are measured at -5$^{\circ}C$, -1$0^{\circ}C$ and -15$^{\circ}C$. Experimental results show that COPs of the system A/C using a PWM method are more effective than those of the inverter method at heating operation mode. Although the heater is on, COPs of PWM method are similar to those of BLDC inverter method. Moreover, the heating capacities of PWM method at -5$^{\circ}C$, -1$0^{\circ}C$ and -15$^{\circ}C$ are larger about 10~20% and outlet air tempe-rature at -15$^{\circ}C$ is larger about 10%, compared to the inverter method.
Keywords
System A/c; PWM; Scroll compressor; BLDC inverter; Heating and low temperature;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Experimental study on the cooling and heating characteristics of system A/C applying the digital scroll compressor /
[ Lee,Y.S.;Kim,D.H.;Jun,Y.H.;Kweon,Y.C.;Chang,K.S.;Moon,J.M.;Yoon,B.;Hong,J.T. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
2 An experimental study on the cooling and heating characteristics of system air-conditioner using the digital scroll compressor /
[ Lee,Y.S.;Jun,Y.H.;Kim,D.H.;Chang,K.S.;Yoon,B.;Moon,J.M.;Hong,J.T.;Oh,M.D. ] / Proceedings of the SAREK
3 Experimental Study on the Efficiency Improvement of DVS System Air-Conditioner Using the Digital Scroll Compressor /
[ Kweon,Y.C.;Lee,Y.S.;Kim,D.H.;Jun,Y.H. ] / Final Report
4 Evaporation heat transfer inside a tube at low evaporating temperature /
[ Moon,D.S.;Seo,J.K.;Kim,Y.C.;Yoon,B. ] / Proceedings of the SAREK
5 A technical prospect and trends in small size heat pump /
[ Hwang,Y.J. ] / The Magazine of the Society of Air-conditioning and Refrigerating Engineers of Korea
6 Multi air-conditioner for cold districts /
[ Hong,K.S. ] / The Magazine of the society of Air-Conditioning and Refrigerating Engineers of Korea
7 Method of Testing for Seasonal Efficiency of Unitary Air Conditioners and Heat Pumps /
[ ASHRAE ] / ASHRAE Standard ANSI/ASHRAE