Browse > Article

The Effect of Non-uniform Superheat on the Performance of a Multi-path Evaporator  

최종민 (한밭대학교 기계공학과)
김용찬 (고려대학교 기계공학과)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.12, 2003 , pp. 1043-1048 More about this Journal
Abstract
An experimental investigation was executed to determine the capacity degradation due to non-uniform refrigerant distribution in a multi-path evaporator. In addition, the possibility of recovering the capacity reduction by controlling the refrigerant distribution among refrigerant paths was assessed. The finned-tube evaporator, which had a three-path and three-depth-row, was tested by controlling inlet quality, exit pressure, and exit superheat for each refrigerant path. The capacity reduction due to superheat unbalance between each path was as much as 30%, even when the overall evaporator superheat was kept at a target value of 5.6$^{\circ}C$. It may indicate that the internal heat transfer within the evaporator assembly caused the partial capacity drop. For the evaporator having air mal-distributions, the maximum capacity reduction was found to be 8.7%. A 4.5% capacity recovery was obtained by controlling refrigerant distribution to obtain the target superheat at the outlet of each path.
Keywords
Evaporator; Superheat; Capacity; Multi-path; Refrigerant flow rate; Air flow rate;
Citations & Related Records
연도 인용수 순위
  • Reference
1 A comparative study of compact enhanced fin-and-tube heat exchangers /
[ Wang,C.C.;Lee,W.S.;Sheu,W.J. ] / Int. Journal of Heat and Mass Transfer   ScienceOn
2 Laboratory methods of testing fans for rating /
[ ANSI ] / ANSI/AMCA 210
3 Impact of air and refrigerant maldistributions on the performance of finned-tube evaporators with R22 and R407C /
[ Lee,J.;Domanski,P.A. ] / Report DOE/CD/23810-81 for ARI
4 A computer model for air-cooled refrigerant condenser with specified refrigerant circuiting /
[ Ellison,P.R.;Crewick,F.A.;Ficher,S.K.;Jackson,W.L. ] / ASHRAE Trans.
5 Study of refrigerant circuitry of evaporator coil with a distributed simulation model /
[ Liang,S.Y.;Wong,T.N.;Nathan,G.K. ] / 7th Int. Refrigeration Conference
6 Methods of Testing for Rating Unitary Air Conditioning and Heat Pump Equipment /
[ ASHRAE ] / ANSI/ASHRAE Standard 37
7 Effect of airflow nonumiformity on evaporator performance /
[ Kirby,E.S.;Bullard,C.W.;Dunn,W.E. ] / ASHRAE Trans.