Browse > Article

Development and Evaluation of a PMV Sensor for the Control of Indoor Thermal Environment  

윤동원 (경원대학교 건축설비학과)
강효석 (경원대학교 건축설비학과)
안병욱 (충청대학 건축학부)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.10, 2003 , pp. 870-878 More about this Journal
Abstract
The maintenance of thermal equilibrium between the human body and its environment is one of the primary requirements for health, wellbeing and comfort. For the effective control of indoor thermal environment, thermostat or humidistat is used. But, it is not sufficient to control the indoor thermal environment using only one or two parameters as human response for the indoor comfortable environment. So an environmental thermal index is required for the control of indoor thermal environment effectively. In this study, a PMV sensor has been developed which has integrated from various kinds of individual sensors for temperature, humidity, air velocity, radiant temperature. After applying the PMV and PPD equation, it is possible to monitor the indoor thermal environment with the sensor system, which is adopted to the circuit for optimization according to the human response with the metabolic rate and activities. The measurement was carried out to verify the performance of the integrated sensor system in comparison with existing measurement system, the PMV meter. As a result, the possibility of applying the PMV sensor to control the indoor thermal environment simultaneously was examined.
Keywords
PMV(predicted mean vote); Indoor thermal environment; PMV sensor;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Ventilation effectiveness and purging flow rate-A review /
[ Mats Sandberg;Mats Sjoberg ] / International Symposium on Room Air Convection and Ventilation Effectiveness
2 Ventilation for acceptable indoor air quality /
[ ASHRAE ] / Standard 62-1989, American Society of Heating
3 Model experiment and numerical simulation of air change efficiency in a room using different air conditioning configurations /
[ Kunio Mizutani ] / 5th International Conference on Air Distribution in Rooms(ROOMVENT'96)
4 The use of moments for assessing air quality in ventilation rooms /
[ Mats Sandberg ] / Building and Environment   ScienceOn
5 Experimental study on indoor thermal environment and ventilation performance of floor-supply displacement ventilation system /
[ Takashi Akimoto ] / Japan Archit. Plann. Environ. Eng.
6 /
[ Fanger,P.O. ] / Thermal Comfort
7 A study of ventilation measurement in an office building /
[ Dols,W.S.;Persily,A.K ] / NISTIR 4905
8 /
[ ASTM ] / E741 Standard test method for determining air change in a single zone by means of tracer gas dilution
9 A numerical calculation on distribution of surface temperature and thermal comfort index caused by radiation iteration in a heated room /