An Experimental Stuff on the Performance of Multi-type Heat Pump using Capillary Tubes  

권영철 (선문대학교 기계공학과)
장근선 (선문대학교 기계공학과)
이윤수 (선문대학교 대학원)
김대훈 (선문대학교 대학원)
전용호 (선문대학교 대학원)
이상재 (산업기술시험원 에너지설비팀)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.14, no.9, 2002 , pp. 749-755 More about this Journal
Abstract
In order to develop a multi-type heat pump system with two indoor units of non-uniform capacities, the optimum refrigerant circuit was developed using capillary tubes. The refrigerant circuit was composed of four main parts, a heating circuit, a cooling circuit, a by-pass circuit and a balance circuit. The system characteristics of multi-type heat pump was investigated through the rating test and the reliability test, using the multi-type psy-chrometric calorimeter. The results of the rating test showed that the capacity of the multi-type heat pump was about 93% of the design value. In particular, the capacity of cooling single mode was about 13% higher than the design value, and the capacity of heating multi mode was about 5% higher than the design value. The reliability of the multi-type heat pump was verified by various reliability tests (overload, extension tube, freeze up, under/over charging, sweat, flood back). The optimal amount of refrigerant charge and compressor capacity were determined from the present work.
Keywords
Mutli-type heat pump; Multi-type calorimeter; Rating test; Reliability test; Capillary tube;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Flow of pure HFC refrigerants and their mixtures through a capillary tube /
[ Chang, S.D.;Ro, S.T. ] / Proceeding of the SAREK ’95 Summer annual Conference
2 Study on Multi-type HVAC System Development /
[ Kweon, Y.C.;Chang, K.S.;Jeong, J.H. ] / RRC Annual Report
3 A photographic study of the two-phase flow of Freon in small bore tubes /
[ Dudley, J.K. ] / M. S. Thesis
4 /
[ Choi, J.Y.;Park, J.U.;Seo, S.M. ] / Air Enthalpy Calorimeter Performance of Sun-moon University
5 Dynamic model of the electric expansion valve for the development of superheat temperature control algorithm /
[ Han, D. ] / proceedings of SAREK
6 Multitype heat pump system computer simulation experimental verification /
[ Han, D.Y.;Chung, M.Y. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
7 Modeling of steady flows of R-22 through capillary tube /
[ Kuehl, S.J.;Goldschmidt, V.W. ] / ASHRAE Trans.
8 Theory and use of the capillary tube expansion device /
[ Bolstad, N.M.;Jordan, R.C. ] / Refrigerating Engineering
9 City multi R-22 pipemulti split type air conditioners for simultaneous cooling and heating operation /
[ Nakamura, T. ] / Refrigeration
10 /
[ KATS ] / Air Conditioners, KS. C930 6
11 Comparison of refrigerant flow through capillary with short tube orifice /
[ Kim, Y.C.;Choi, J.M. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
12 /
[ Stoecker, W.F.;Jones, J.W. ] / Refrigeration and Air Conditioning
13 Performance Analysis of a Multi-type Inverter Heat Pump /
[ Kim, Y.C.;Par, K.W.;Yun, Y.;Min, M.G.;Choi, Y.D. ] / Korean Journal of Air-Conditioning and Refrigeration Engineering   과학기술학회마을
14 Investigation of the Performance of Capillary Tube with the Roughness Effect /
[ Kim, C.N.;Hwang, E.P. ] / Proceeding of the SAREK '95 Summer annual Conference