Browse > Article
http://dx.doi.org/10.1016/j.net.2019.03.012

Seismic performance of emergency diesel generator for high frequency motions  

Jeong, Young-Soo (Seismic Research and Test Center, Pusan National University)
Baek, Eun-Rim (Seismic Research and Test Center, Pusan National University)
Jeon, Bub-Gyu (Seismic Research and Test Center, Pusan National University)
Chang, Sung-Jin (Seismic Research and Test Center, Pusan National University)
Park, Dong-Uk (Seismic Research and Test Center, Pusan National University)
Publication Information
Nuclear Engineering and Technology / v.51, no.5, 2019 , pp. 1470-1476 More about this Journal
Abstract
The nuclear power plants in South Korea have been designed in accordance with the U.S. Regulatory Guide 1.60 (R.G 1.60) design spectrum of which the peak frequency range is 2-10 Hz. The characteristics of the earthquakes at the Korea nuclear power plant sites were observed to be closer to that of Central and Eastern United States (CEUS) than the R.G 1.60, which is a lower amplification in a low frequency range, and a higher amplification in a high frequency range. The possibility of failure for sensitive power plant components in the high frequency range has been considered and evaluated. In this study, in order to improve the reliability of nuclear plant and administrative control procedures, seismic tests of an emergency diesel generator (EDG) were conducted using a shaking table under both high and low frequency ranges. From the tests, oil/lubricant leaks from the bolt connections, the fuel filter and the fuel inlet were observed. Therefore, the check list of nuclear plant components after an earthquake should include bolt connections of EDG as well as anchor bolts.
Keywords
Emergency diesel generator; Seismic performance; High frequency motion; Shaking table test;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 International atomic Energy agency (IAEA) and nuclear Energy agency (NEA), Nucl. Power Plant Oper. Exp. (2002).
2 ACI 318, Building Code Requirements for Structural Concrete and Commentary, 2014.
3 Y. Shimada, Trend analyses of the emergency diesel generator problem events in Japanese and U.S. Nuclear power plants, J. Inst. Nucl. Saf. Syst. 18 (2011) 267-274.
4 C.S. Mueller, O.S. Boyd, M.D. Petersen, M.P. Moschetti, S. Rezaeian, A.M. Shumway, Seismic hazard in the eastern United States, Earthq. Spectra 31 (2015) 85-107.   DOI
5 C.G. Lee, Earthquake engineering analysis of ground accelerations measured in the 912 Gyeong-ju earthquake, Mag. KSCE Spec. Featur. 65 (4) (2017) 8-13 (in Korean).
6 R.K. McGuire, W.J. Silva, C.J. Costantino, Technical Basis for Revision of Regulatory Guidance on Design Ground Motions: Hazard- and Risk-Consistant Ground Motion Spectra Guidelines, NUREG/CR-6728, 2001.
7 US NRC Regulatory Guide 1.60, Design Response Spectra for Seismic Design of Nuclear Power Plants, 1973.
8 N.M. Newmark, W.J. Hall, Development of criteria for Seismic Review of Selected Nuclear Power Plants, USNRC Report NUREG/CR-0098, US Nuclear Regulatory Commission, 1978.
9 J.W. Reed, R.P. Kennedy, B. Lashkari, Analysis of High-Frequency Seismic Effects, EPRI TR-102470, 1993.
10 M.K. Kim, Y.S. Choun, Operating vibration reduction effect evaluation of EDG at the NPP site, in: Proceedings of the KSNVE Annual Autumn Conference, 2006, pp. 111-118.
11 IEEE 323, IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generation Stations, 2010.
12 IEEE 287, IEEE Standard for Criteria for Diesel Generator Units Applied as Standby Power Supplies for Nuclear Power Generation Stations, 2017.
13 D.C. Lee, M.J. Brennan, B.R. Mace, A design criterion for the vibration isolation of a marine diesel generator set, Trans. Kor. Soc. Noise Vib. Eng. 16 (4) (2006) 329-338 (in Korean).   DOI
14 C.S. Kim, H.O. Choi, H.H. Jung, A study of analytical integrity estimations for the structure and rotor system of an emergency diesel generator, Trans. Kor. Soc. Noise Vib. Eng. 24 (2) (2014) 79-86 (in Korean).   DOI
15 U.S. NRC Regulatory Guide 1.9, Application and testing of safety-related diesel generators in nuclear power plants, Rev 4 (2000).
16 W. Liu, T.S. Aziz, Seismic Capacity of Emergency Power Supply Diesel Generator Set for Candu, 19th International Conference on Structural Mechanics in Reactor Technology, 2007. K11/6.
17 T. Iwatsubo, Damage to industrial equipment in the 1995 hyogoken-nanbu earthquake, Nucl. Eng. Des. 181 (1998) 41-53.   DOI
18 M.K. Kim, I.K. Choi, A shaking table test for an Re-evaluation of seismic fragility of electrical cabinet in NPP, Comput. Struct. Eng. Inst.Korea 24 (3) (2001) 295-305 (in Korean).
19 H.M. Rhee, M.K. Kim, D.H. Sheen, I.K. Chol, Analysis of Uniform hazard spectra for metropolises in the Korean peninsula, J. Earthq. Eng. Soc. Korea 17 (2) (2013) 71-77.   DOI
20 S. Kawakami, F. Hara, H. Shibata, Y. Ono, Y. Horimizu, T. Ichihasi, Y. Uchiyama, T. Niino, M. Takayanagi, Y. Kahimura, K. Meada, Seismic proving test of emergency diesel generator system, in: 12th International Conference on Structural Mechanics in Reactor Technology, 1993. K15/6.
21 European Clearinghouse on NPP Operational Experience Feedback, Topical Operation Experience Report on Events Related to Emergency Diesel Generators, DG-JRC, IET-Petten, 2013.
22 M.K. Kim, Y.S. Choun, 2007, shaking table test of isolated EDG model, J. Earthq. Eng. Soc.Korea 11 (3) (2007) 33-42 (in Korean).
23 IEEE 344, IEEE Standard for Seismic Qualification of Equipment for Nuclear Power Generating Stations, 2013.