Study on the energy-saving constant temperature and humidity machine operating characteristics  

Cha, Insu (Department of Hydrogen Energy, DongShin University)
Ha, Minho (Department of Energy Environment Engineering of Graduate school, Dong Shin University)
Jung, Gyeonghwan (Department of Energy Environment Engineering of Graduate school, Dong Shin University)
Publication Information
Abstract
The heat recovery system that was applied in this study, is the energy-saving type that can produce the maximum cooling capacity less power in use. In order to have a more precise control function the temperature and humidity of the constant temperature and humidity machine, control algorithm is applied to designed a fuzzy PID controller, and the outside air compensation device (air-cooled) demonstrated excellent ability to dehumidify the moisture, $-20^{\circ}C$ in winter. High efficiency and the low-noise type sirocco fan operate quitely and designed to fit the bottom-up and top-down in accordance with the characteristics of equipment. as a result of experiment data, the conversion efficiency is 95% or more, power recovery time is within 5sec, stop delay time is within 30sec, pump down time is 10sec, pump delay time is 5sec, heating delay time is 5sec, temperature deviation is ${\pm}2^{\circ}C$ (cooling deviation: $2^{\circ}C$, Heating deviation : $2^{\circ}C$), humidity deviation is a ${\pm}5%$ (humidification deviation 3.0%, dehumidification deviation 3.0%). Recently, ubiquitous technology is important. so, the constant temperature and humidity machine designed to be able to remotely control to via the mobile phone, and more scalable to support MMI software and automatic interface. Further, the life of the parts and equipment is extended by the failure.
Keywords
temperature and humidity machine; heat recovery type; fuzzy PID controller; Operating characteristics; Energy-saving;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Kwang-ho Hong, 2001, A study on the control of the temperature and humidity using the fuzzy PID algorithm, Kum-oh National University of Technology (in Korean), PP. 4-9
2 Kang Yong-ju, Kim Yong-jin, 1995, Constant Temperature - Humidity Controller, SAREK, PP. 49-57
3 Younggy Shin, Young-Soo Chang, Youngil Kim, 2002, An improved control logic for a constant temperature and humidity unit, SAREK, Vol. 2002 PP. 363-368
4 Son, Deok-shin, 1986, Fact of the constant temperature and humidity machine, KARSE, Vol. 3, No. 11, PP. 51-59
5 P. Basehore, 1993, Fuzzy Logic Outperforms PID Controller, PCIM, March
6 C.C Lee, 1990, Fuzzy Logic in Control Systems(IEEE Trans. on Systems, Man, and Cybernetics), SMC, Vol. 20, No. 2, pp. 404-409