Browse > Article
http://dx.doi.org/10.5293/kfma.2014.17.5.011

Study on Optimal Design and Performance Test of Chilled Beam Unit  

Kim, Jung-Yup (Korea Institute of Civil Engineering and Building Technology)
Shin, Hyun-Jun (Korea Institute of Civil Engineering and Building Technology)
Joo, Sang-Hyun (Korea Institute of Civil Engineering and Building Technology)
Kim, Ji-Seok (Korea Institute of Civil Engineering and Building Technology)
Publication Information
Abstract
Chilled Beam system is the kind of water-air system which reduces the conveyance energy for air conditioning as well as allows efficient installation and comfortable indoor environment, and has been increasingly popular mainly in Europe. To effectively install such Chilled Beam system domestically, it is necessary to develop the product considering domestic climatic condition and the requirements for air conditioning system, and particularly the way to deal with condensation during operation of cooling system in summer shall be provided. In this study, the optimal design on induction structure of Chilled Beam unit was carried out through a numerical method, and the performance test for the prototype of unit was conducted in a real-scale experiment facilities of Chilled Beam unit. While the flowrate of 1st air is 101.3 CMH, the pressure in pressure chamber is 158.7 Pa and the cooling capacities of 1st air side and 2nd air side are 498.1 W and 709.5 W respectively.
Keywords
Chilled beam; HVAC system; Induction ratio; Energy saving; Real-scale experiment;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Hong, S. G., Kwon, B. Y., Kim, G. M, Yoon, Y. W., Shin, H. J., Kim, J. Y., 2005, "HVAC system to lower the conveyance energy and control fresh-air flow rate quantitatively," SAREK HARFKO Proceedings, 2005 April, pp. 588-598.
2 Cho, J. K., Jeong, C. S., Kim, B. S., 2008, "The energy conservational HVAC system design approaches of the large-scale buildings," Journal of Architectural Institute of Korea, Vol. 24, No. 6, pp. 347-354.   과학기술학회마을
3 Kavanaugh, S., 2000, "Fan demand and energy: three air-distribution systems," ASHRAE Journal, Vol. 42, No. 6, pp. 47-52.
4 Kim, J. Y., Shin, H., J., 2003, "Development of HVAC system to lower the conveyance energy and building height," Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 15, No. 2, pp. 116-525.   과학기술학회마을
5 Alexander, D., Rourke, M., 2008, "Design considerations for active chilled beams," ASHRAE Journal, Vol. 50, No. 8, pp. 50-58.
6 Rumsey, P., Weale, J., 2007, "Chilled beams in labs: eliminating reheat and saving energy on a budget," ASHRAE Journal, Vol. 49, No. 1, pp. 18-25.
7 Son, K., H., "Chilled beam system," Journal of Korean Architectural Institute, Vol. 41, No. 5, pp. 108-111.
8 Kim, J. Y., Shin, H., J., Kim, J. S., Joo, S. H., 2013, "Study on Induction Capability of Chilled Beam HVAC System," Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 25, No. 5, pp. 255-260.   과학기술학회마을   DOI   ScienceOn