Browse > Article
http://dx.doi.org/10.5293/KFMA.2009.12.5.025

Effect of the Suction Performance by the Air-Curtain Blowing around a Suction Duct  

Cho, Chong-Hyun (경상대학교 대학원)
Kim, Chae-Sil (창원대학교 기계공학부)
Cho, Soo-Yong (경상대학교 항공기부품기술연구센터(기계항공공학부))
Publication Information
Abstract
A study is conducted to improve the suction performance on suction devices which are used to remove polluted air generated by welding or machining process in a spacious working place of industry. Air-curtain is applied around the inlet of suction duct to interrupt the inflow of fresh air from the downstream region where is located opposite to the polluted air source. Two different air-curtain devices, such as a $45^{\circ}$ backward and a fully backward, are adopted. Suction region is experimentally investigated by measuring the suction velocities using a hot-wire anemometer. Contours of the suction velocity are compared with the computed results. The suction condition is selected to 110,000 Reynolds number which is widely used on typical suction devices, and a width of blowing passage for creating the air-curtain is chosen to 9.38% of the suction duct diameter. The experimental results show that the suction performance obtained with the $45^{\circ}$ backward air-curtain was better than that obtained with the fully backward air-curtain. On the suction duct using the $45^{\circ}$ backward air-curtain, the suction region estimated on basis of the 0.4m/sec is improved by 66% at the same input power.
Keywords
Suction Performance; Air-Curtain; Ventilation; Suction Region; Polluted Air;
Citations & Related Records
연도 인용수 순위
  • Reference
1 조종현, 김재실, 조수용, 2008, '흡입관의 형상에 따른 흡입 성능에 대한연구,' 대한설비관리학회지, Vol 13, No. 3, pp. 67-78
2 조종현, 정양범, 조수용, 2009, '흡입성능향상을 위한 공기차 단막의 효과에 관한연구,' 한국실내환경학회지, Vol, 6, No. 1, pp. 27-37
3 CFX -11, 2007, Ansys
4 Menter, F. R., 1994, 'Two-Equation Eddy- Viscosity Turbulence Models for Engineering Applications,' AIAA J. Vol 32, No. 8, pp. 1598-1607   DOI   ScienceOn
5 김수용,정상현,최범석,박무룡,2000, '와류유동을 이용한 환기시스템개발,' 한국기계연구원연구보고서 2000-01-31
6 Li Y. and Desante, A, 1996, 'Derivation of capture Efficiency of Kitchen Range Hoods in a Confined Space,' Building and Environment, Vol 31, No. 5 pp. 461   DOI   ScienceOn
7 함진식, 2001, '흡기용 에어커벤이 렌지후드의 환기성능에 미치는 영향에 관한 연구,' 대한 건축학회논문집, 계획계 Vol 17, No. 6 pp. 153 -160
8 Chokhar, I. A., Prozorov, D. S., Spotar, S. Y., 1993, 'An Efficient Extraction of Furnes by Means of The Vortex Suction Device,' Russian Academy of Science
9 Hijikata, K. and Suzuki,Y., 1995,'Local Ventilation and Heat Transfer by Tomado-Like Vortex,' ASME/JSME Thermal Engineering Conference, Volurne 1