Browse > Article
http://dx.doi.org/10.5293/KFMA.2006.9.3.044

Selection of Centrifugal Fan for Flows with Down-Stream Resistance  

Kim Jae-Won (선문대학교 기계공학부)
Jang Dong-Hee (선문대학교 대학원 기계공학과)
Ahn Eun-Young (한밭대학교 멀티미디어학과)
Publication Information
Abstract
Comprehensive experimental works are carried out for the optimal design of a centrifugal blower adopted in an indoor unit of an air-conditioner. The models for consideration are typical multi-blade turbo blower and limit loaded one, respectively. The main interest lies on the fluid dynamics performance when the blower Is installed in the practical system. The methodologies are an experimental estimations with a wind tunnel for blower performance and PIV measurement for the detail flow information. A centrifugal blower with limit loaded fan shows pronounced performances in terms of the flow rate and static pressure rise and the reason is explained by the precise measurement of the flows between blades using PIV. Consequently, it is found that the blower is proper for the flows with a resistance in down stream such as a heat exchanger.
Keywords
Centrifugal Blower; Fluid Dynamics Performance; PIV; Wind Tunnel;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Hemant Kale, 2004, 'Considerations In Designing Next Generation finned, Copper, Tube Heat Exchangers,' Appliance magazine, October, pp. 1-5
2 TSI, 2003, Insight 5.5 - Particle Image Velocimetry User Manual
3 Iizuka, T., Nomura, T., Ishima, T., Obokata, T., Suzuki, T., and Shimizu, J., 2002, 'Measurements of Flow around a Cooling Fan Rotor in the Duct by Means of PIV and LDA,' Visualization Society of Japan, Vol. 22, SUP. 1 pp. 401-404   DOI
4 Choudhuri, P. Ghosh, and Knight, D. D., 1994, 'Two-Dimensional Unsteady Leading-Edge Separation on a Pitching Airfoil,' AIAA Journal, Vol. 32, No.4, pp, 673-681   DOI   ScienceOn
5 Harada, S., 1999, Fluid Machinery, Asakura Publishing Company, pp. 174-179
6 ASHRAE Standards, 1975, 'Laboratory Methods of Testing Fans for Rating Purposes,' ASHRAE, I, 54-75, I, pp. 1-57
7 Kim, J. W. and Jeong, Y. Y, 2000, 'Performance and Flow Characteristics of Axial Fan,' Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 12, No 11, pp. 972- 981   과학기술학회마을