A CFD Simulation Study on the Isolation Performance of a Isolation Ward  

Sohn, Deokyoung (Department of Mechanical Engineering, Ajou University)
Kwon, Soonjung (Department of Architecture, Ajou University)
Choi, Yunho (Department of Mechanical Engineering, Ajou University)
Publication Information
Journal of The Korea Institute of Healthcare Architecture / v.20, no.1, 2014 , pp. 7-14 More about this Journal
Abstract
Purpose: In this study, we performed ventilation simulations for a standard isolation ward including three intensive care rooms, one anteroom(buffer room), and its recommended ventilation equipments. The purpose of this study is to predict outflow of pathogenic bacteria from patient breath to verify the reliability and the safety of the isolation ward. Methods: We suppose three scenarios of the movement of medical staff. The leakage of patient's breath to out of the ward is predicted in these scenarios using CFD simulations. Results: The patient's breath leakage rate to out of the ward in scenario 1 according to room air changes per hour(ACH : 6 and 12) is predicted to be 0.000057% and 0.00002%, respectively. The patient's breath leakage rate to out of the ward in scenario 2 according to room air changes(ACH : 6 and 12) is predicted to be 0.00063% and 0.00019%, respectively. The patient's breath leakage rate to out of the ward in scenario 3, which is the worst case(6 room air changes) is predicted to be 0.1%. Implications: Through the ventilation simulation like that in this study, the reliability and the safety on isolation performance of various plan of isolation ward are predicted quantitatively.
Keywords
CFD simulation; Isolation ward; Ventilation; Room air change per hour;
Citations & Related Records
연도 인용수 순위
  • Reference
1 김진균(Kim, J), 초고층 건축물 건설기술 연구단 최종 보고서(3세부과제: 환경 및 에너지 절감기술), 2003
2 정종림(Jeong, J), 종합병원의 환기설비 사례 연구, 한국생태환경건축학회 논문집, 4(3):187, 2004
3 질병관리본부, 거점병원 지원 시설기준, 2010
4 한화택(Han, H), 난류유동해석을 통한 환기효율의 수치해석적 연구, 공기조화, 냉동공학 논문집, 4(4):253-262, 1992
5 AIA. Guidelines for Design and Construction of Health Care Facilities, American Institute of Architects, 2006.
6 Centers for Disease Control and Prevention(CDC) and Healthcare Infection Control Practices Advisory Committee(HICPAC). Guidelines for Environmental Infection Control in Health-Care Facilities, 2003