Abstract
Purpose: This study was conducted to analyze the air flow characteristics in a plant factory with different inlet and outlet locations using computational fluid dynamics (CFD). Methods: In this study, the flow was assumed to be a steady-state, incompressible, and three-dimensional turbulent flow. A realizable k-${\varepsilon}$ turbulent model was applied to show more reasonable results than the standard model. A CFD software was used to perform the numerical simulation. For validation of the simulation model, a prototype plant factory ($5,900mm{\times}2,800mm{\times}2,400mm$) was constructed with two inlets (${\Phi}250mm$) and one outlet ($710mm{\times}290mm$), located on the top side wall. For the simulation model, the average air current speed at the inlet was $5.11m{\cdot}s^{-1}$. Five cases were simulated to predict the airflow pattern in the plant factory with different inlet and outlet locations. Results: The root mean square error of measured and simulated air current speeds was 13%. The error was attributed to the assumptions applied to mathematical modelling and to the magnitude of the air current speed measured at the inlet. However, the measured and predicted airflow distributions of the plant factory exhibited similar patterns. When the inlets were located at the center of the side wall, the average air current speed in the plant factory was increased but the spatial uniformity was lowered. In contrast, if the inlets were located on the ceiling, the average air current speed was lowered but the uniformity was improved. Conclusions: Based on the results of this study, it was concluded that the airflow pattern in the plant factory with multilayer cultivation shelves was greatly affected by the locations of the inlet and the outlet.
Keywords
Airflow; Computational fluid dynamics (CFD); Plant factory; Turbulent model;
Citations & Related Records
Times Cited By KSCI : 6  (Citation Analysis)
연도 인용수 순위
1 Boulard, T. and S. Wang. 2002. Experimental and numerical studies on the heterogeneity of crop transpiration in a plastic tunnel. J. Computers and Electronics in Agriculture 34:173-190.   DOI
2 Choi, J.M. and S.W. Cho. 2009. A study on the indoor airflow pattern by changing the location of mechanical terminal unit. J. of Air-Conditioning and Refrigerating 21(3):193-200 (In Korean).   과학기술학회마을
3 Kim, Y.H. and Kozai, T. 1996. Effects of air current speed on the microclimates of the plug stand under artificial light. J. of Bioproduction Facility and Environment 5(2):160-166 (In Korean).   과학기술학회마을
4 Kwon, K.S., I.B. Lee, H.S. Hwang, J.P. Biotg, S.W. Hong, I.H. Seo, J.S. Choi, S.H. Song and O.G. Moon. 2010. Analysis on the optimum location of a wet air cleaner in a livestock house using CFD technology. J. of the Korean Society of Agricultural Engineers 52(3):19-29 (In Korean).   과학기술학회마을   DOI
5 Kim, H.J., Y.I. Kim and K.S. Chung. 2010. Effect of location and size of the inlet and outlet diffusers on ventilation flow rate of a box type space. Proceedings of the SAREK(Spring) pp.311-316 (In Korean).
6 Kim, Y.H. 1998. Effects of air current speeds on the growth of eggplant plug seedlings in a wind tunnel under artificial lighting. J. of Bioproduction Facility and Environment 7(1):9-14 (In Korean).   과학기술학회마을
7 Kim. Y.H. and Kozai, T. 1997. Measurement of net photosynthetic rate in the plug stand. J. of Agricultural Machinery 22(3):311-316 (In Korean).   과학기술학회마을
8 Kozai, T. 2013. Plant factory in Japan - Current situation and perspectives. Chronica Horticulturae 53(2):9-11.
9 Lee, I.B. 2013. Trend on CFD application in agriculture. Rural Resources 55(1):51-57 (In Korean).   과학기술학회마을   DOI
10 Park, D.Y., S.T. Jang and S.J. Chang. 2013. Numerical study on the thermal environment of a natural light based multi-layered plant factory. J. of Korea Institute of Ecological Architecture and Environment 13(5):43-50 (In Korean).   과학기술학회마을   DOI
11 Yun, N.G. 2002. Design and analysis technique for greenhouse environment using CFD simulation. J. of Kor. Res. Soc. Protected Hort. 15(1):20-26 (In Korean).
12 Park, J.H., J.S. Lee, D.E. Kim and Y.H. Kim. 2011. Analysis of optimum water cooling conditions and heat exchange of LED lamps for plant growth. J. of Biosystems Eng. 36(5):334-341 (In Korean).   과학기술학회마을   DOI   ScienceOn
13 Shih, T.H., W.W. Liou, A. Shabbir, Z. Yang and J. Zhu. 1995. A new k-${\epsilon}$ eddy viscosity model for high Reynolds number turbulent flows: model development and validation. Computers & Fluids 24(3):227-238.   DOI   ScienceOn
14 Yun, H.S., J.K. Kwon, H. Jeong, D.H. Lee, Y.K. Kim and N.K. Yun. 2007. CFD simulation of airflow and heat transfer in the cold container. J. of Biosystems Eng. 32(6): 422-429 (In Korean).   과학기술학회마을   DOI